Tandem door air curtains
Door air curtains with patented Tandem technology
Assembly, installation and operating instructions
29
7
Electrical wiring
IMPORTANT NOTE!
Only pulse and/or all-current sensitive residual current protective devices (type A or B) are permitted. It is
impossible to protect personnel when operating the unit with residual-current protection devices, as well as
with frequency converters.
When power is applied to the unit, pulse-like capacitor load currents in the integrated EMC filter of the EC
fans can lead to the RCCB being immediately tripped.
We recommend residual current protective switches with a threshold of 300 mA and delayed triggering (su-
per resistant, characteristic K).
IMPORTANT NOTE!
If the fan is activated from idle by a door contact, a certain time is needed before a door air curtain can
provide actual screening. When operating via a door contact, set operation as basic speed to forced boost
(possible with compact controller type 30158 and KaControl).
7.1
Maximum electrical rating values
Description
Model
Number of fans
Voltage
Output
Electri-
city
Ri (*00)
Ri (*T)
Tandem 300, Tandem
ceiling cassette unit
12
1 x TD
230 V AC 50/60 Hz
250 W
1.8 A
100 KΩ
100 KΩ
20
2 x TD
230 V AC 50/60 Hz
500 W
3.6 A
50 KΩ
100 KΩ
25
3 x TD
230 V AC 50/60 Hz
750 W
5.4 A
33 KΩ
100 KΩ
30
3 x TD
230 V AC 50/60 Hz
750 W
5.4 A
33 KΩ
100 KΩ
Tandem 365
12
1 x TD
230 V AC 50/60 Hz
400 W
2.5 A
100 KΩ
100 KΩ
20
2 x TD
230 V AC 50/60 Hz
800 W
5.0 A
50 KΩ
100 KΩ
27
3 x TD
230 V AC 50/60 Hz
1200 W
7.5 A
33 KΩ
100 KΩ
Insulate valve drive
normally closed (N/C)
-
-
230 V AC 50/60 Hz
1 W
0.55 A
- KΩ
- KΩ
Tab. 7: Maximum electrical rating values