Katherm HK
Ready-to-install trench heaters with EC tangential fan
Assembly and installation instructions
9.2.3 On-site condensation drainage with a natural gradient
The following drawing shows the on-site condensation connection of the
Katherm HK with a natural gradient to a condensation collecting pipe.
min 2% Gefälle
min 2% Gefälle
1
2
3
1
2
3
Kondensatanschluss Katherm HK - Sammelleitung
Kondensatsammelleitung
Achtung! Anschluss der Kondensatsammelleitung an das Schmutzwassernetz nach den
gültigen Normen und Regeln; Beachtung von notwendigen Entlüftungen,
Geruchsverschlüssen (Siphon), ect.
3
2
1
1
Katherm HK condensation connection – collecting pipe
2
Condensation collecting pipe
3
Important
: Connect the condensation collecting pipe to the waste water
network in accordance with all applicable technical standards and regulations;
note in particular any necessary vents, traps etc.
min. 2% gradient