 KaDeck  Ceiling 

Cassette

Installation and operating instructions

Keep these instructions in a safe place for future use!

Kampmann.gb/installation_manuals

I506 

12

/

16

/1 GB SAP-Nr. 1221711

Summary of Contents for KaDeck Series

Page 1: ...KaDeck Ceiling Cassette Installation and operating instructions Keep these instructions in a safe place for future use Kampmann gb installation_manuals I506 12 16 1 GB SAP Nr 1221711...

Page 2: ...2 1 Danger from electrical energy 8 2 3 Responsibility of the operator 8 2 4 Instruction 9 2 5 Personnel requirements 10 2 5 1 Qualifications 10 2 6 Personal protective equipment 10 3 Technical data 1...

Page 3: ...29 6 7 Electrical wiring 30 6 8 Overview of controls 32 7 Operation and commissioning 39 7 1 Pre commissioning checks 39 7 2 Venting the heat exchanger 40 7 3 Switching on 41 8 Maintenance 41 8 1 Sec...

Page 4: ...safety instructions and other instructions contained in this manual In addition all local occupational health and safety at work regulations apply as do general safety provisions governing the use of...

Page 5: ...ustomer Service team is available is available for technical information We are always interested in receiving information and experiences relating to the use of our products which could be of value f...

Page 6: ...these instructions Any use beyond or other than the stated intended use is considered misuse 2 2 Performance data Operating limits max operating pressure 10 bar min entering water temperature 6 C min...

Page 7: ...content Never operate the unit in rooms that contain high temperature gases Never operate the unit in aggressive or corrosive atmospheres e g sea air Never operate the unit above electrical equipment...

Page 8: ...to implement this in the form of operating instructions for the operation of the unit The operator must regulate and specify the responsibilities for installation operation troubleshooting maintenanc...

Page 9: ...pecifications in line with the pertinent legal standards and guidelines relating to hygiene applicable at the installation site This includes ensuring that fresh and waste water are hygienically separ...

Page 10: ...asks and independently recognise possible dangers Installation personnel have all the necessary equipment and tools Caretakers users Caretakers users have been instructed by the manufacturer in the ta...

Page 11: ...terdeckenger t einseitig ausblasend Zwischendeckenger t zweiseitig ausblasend Zwischendeckenger t einseitig ausblasend Vorderansicht Vorderansicht Vorderansicht Vorderansicht Ansicht von oben Ansicht...

Page 12: ...asend Vorderansicht Vorderansicht Vorderansicht Vorderansicht Ansicht von oben Ansicht von oben Ansicht von oben Ansicht von oben Weights Connections female thread Eurokonus same end connections on ri...

Page 13: ...um Medium 5 Minimum Control voltage V 10 8 6 4 2 10 8 6 4 2 Air volume V m h 635 525 418 308 199 369 297 225 152 79 Power consumption P W 30 27 14 7 5 30 27 14 7 5 Speed n rpm 1100 925 750 575 400 110...

Page 14: ...um 5 Minimum Control voltage V 10 8 6 4 2 10 8 6 4 2 Air volume V m h 565 467 371 274 177 369 297 225 152 79 Power consumption P W 30 27 14 7 5 30 27 14 7 5 Speed n rpm 1100 925 750 575 400 1100 925 7...

Page 15: ...r offices and administration buildings Installation and operating instructions 4 Construction and function 4 1 Overview 1 2 4 5 3 3 Connecting frame Ceiling panel Air outlets Invisible latches Invisib...

Page 16: ...ed so that no additional service hatches are needed 7 Fresh air connection All models have a possible fresh air supply from above The suspended ceiling versions also offers the option of side connecti...

Page 17: ...is drawn in by the fan located directly downstream of the filter and pressed through the copper aluminium heat exchanger Depending on at which temperature the medium flows through the heat exchanger...

Page 18: ...ar to RAL 9010 large LCD multifunctional display integral room temperature sensor communication interface to the Kampmann T LAN bus system automatic switching LED background lighting push dial navigat...

Page 19: ...ewpoint monitor sensor Cable length 10 m included in all KaDecks with KaControl and dewpoint monitor sensor KaControl room temperature sensor wall mounted IP30 surface mounted colour white RAL 9010 Al...

Page 20: ...terial damage caused by incorrect transport Units being transported can drop or topple over if transported wrongly This can cause serious material damage Proceed carefully when unloading the equipment...

Page 21: ...and other damage before they are assembled Therefore do not destroy the packaging and only remove shortly before installation Handling packaging materials Dispose of packaging materials in line with...

Page 22: ...it Chapter 3 Technical Data on page 11 ff The load proof and vibration free position of the unit is guaranteed possibly call in the services of an architect or structural engineer also in connection w...

Page 23: ...air outlet to avoid the creation of draughts The throw diagrams can help with this Select and position the unit taking into account where people will be standing and sitting If the distance from the...

Page 24: ...skartondecke wird ein entsprechender Ausschnitt nach nebenstehenden Ma en erstellt With a rigid plasterboard ceiling a corresponding cut out is produced in line with the adjacent dimensions Fit the su...

Page 25: ...If the temperature falls below the dew point on the heat exchanger the dew point monitor switches off the cooling valve The dew point monitor does not act as a controller and even if a dew point senso...

Page 26: ...ng sealing work and then the angle valve to the KaDeck Now the actuator can be fitted and the cable routed to the electrical connection area Use the clamps on the fan for this purpose Now fit the comp...

Page 27: ...e 3 are fitted and sufficiently fixed in place Check whether the foam tape provides a seal between the fan and fan unit It may be necessary to press it into place a little The water connections as wel...

Page 28: ...pliance with the operating limits of the KaDeck 22 Pla mpmann de K hlbetrieb Taupunktw chter montiert ab Werk Kondensatwanne Kondensatpumpe Optional bei Regelungsausstattung KaControl m glich Nein Nei...

Page 29: ...m Flansch erfolgen Dazu wird die Anstanzung an der Oberseite des Ger tes entfernt Bei den Zwischendeckenvarianten ist zudem ein Anschluss von der Seite m glich Hierzu ist das Zubeh r des Prim rluftstu...

Page 30: ...e the KaController as a room control unit in conjunction with Kampmann systems KaControllers can only be used indoors e g in residential and commercial properties showrooms etc KaControllers cannot be...

Page 31: ...TABs issued by the regional electricity providers Protect the products from any moisture during installation Check the intended use with the manufacturer in case of any doubt Any use other than the us...

Page 32: ...k a qualified electrician to determine the type of cable and cable cross sections the cable cross sections basically depend on the fuses for the cable length and the wiring capacity of the electric mo...

Page 33: ...means of an external 0 100 kOhm potentiometer signal on the AI2 GND and AI3 GND input see separate KaControl instructions Activation by potentiometer 0 100 kOhm ON 3 Clip on sensor fitted ON OFF The...

Page 34: ...he DIP switches on the rear of the KaController as shown on the diagram at the side DIP switch no 1 ON DIP switch no 2 OFF GEFAHR Disconnect the KaDeck prior to embarking on any wiring work Only conne...

Page 35: ...ature for each unit via a room or air intake sensor Temperature detection with group control The air intake temperature is used for regulation with group control Every ceiling cassette regulates based...

Page 36: ...e DIP switches on all CANbus cards in a control circuit identically DIP switch on the rear side of the CANbus card DIP1 ON DIP2 OFF DIP3 OFF DIP4 OFF DIP5 OFF DIP6 OFF DIP7 OFF DIP8 ON DIP9 OFF DIP10...

Page 37: ...Both control units can be used to call up all functions with the keys offering the possibility of quick access to some functions 1 2 3 4 5 6 7 1 5 No Description 1 Display of the operating mode set 2...

Page 38: ...emperature Confirm the entry by pressing the navigator dial Fan speed Change by pressing the side fan button or using the navigator dial Briefly press the navigator dial once Turn the navigator dial t...

Page 39: ...with the applicable regulations Are all wires connected in accordance with the electric wiring diagrams Is the protective conductor connected and wired throughout Water side test Is the flow and retu...

Page 40: ...7 2 Venting the heat exchanger Open all on site shut off devices and valves Hold a receptacle in place to catch any water that escapes and protect the environment from spraying water Then open the ven...

Page 41: ...ns Always follow the procedure described below to prevent accidental restart 7 3 Switching on Switch on the mains voltage Start up the unit using the control unit connected Check the fan speeds by swi...

Page 42: ...l unit Caretakers users Regular visual inspection of the fixing and examination of damage Caretakers users quarterly Visual check of the filter replacing as necessary or cleaning Caretakers users ever...

Page 43: ...ge corrosion and leak tightness and clean if necessary 3 months With wet cooling units check heat exchangers condensation tray and drain for dirt damage corrosion and leak tightness and clean if neces...

Page 44: ...operating instructions 8 3 1 Changing filters Switch off unit before opening the intake cover 1 Open the intake cover until the securing catch snaps into place 2 Press the securing hook to the inside...

Page 45: ...disc 3 Check water connections and lines for leaks 4 Check that the heat exchanger is clean and if necessary clean Dusty and greasy deposits on the fins of the heat exchanger impair the airflow and h...

Page 46: ...eceptacle ready to catch any water Remove the flat switch by removing the cable tie and allow all water to drain into the container Water will flow from the condensation tray as well as from the float...

Page 47: ...applies 1 Immediately switch off the unit with faults that pose animmediate danger to persons or property 2 Determine the cause of the fault 3 Switch off the unit and prevent if from being reconnected...

Page 48: ...an not switched on Switch on fan at controller User Caretaker Air volume too low Set higher fan speed Filter dirty Replace filter No heating or cooling medium Switch on heating and or cooling system s...

Page 49: ...andle open sharp edged components carefully Make sure that the workplace is clean and tidy Components and tools stacked loosely or spread around tools represent a source of accidents Dismantle the com...

Page 50: ...and dispose of other components IMPORTANT NOTE Environmental hazard from incorrect disposal Incorrect disposal can present a hazard to the environment Electrical scrap electronic components lubricants...

Page 51: ...51 KaDeck 3 26 Versatile air conditioning for offices and administration buildings Installation and operating instructions 11 Declaration of Conformity...

Page 52: ...52 3 26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions...

Page 53: ...53 KaDeck 3 26 Versatile air conditioning for offices and administration buildings Installation and operating instructions...

Page 54: ......

Page 55: ......

Page 56: ...ich Ebert Str 128 130 49811 Lingen Ems Germany T 49 591 7108 0 F 49 591 7108 300 E info kampmann de W Kampmann de Kampmann UK Ltd Dial House Govett Avenue Shepperton Middlesex TW17 8AG Great Britain T...