Raumtherm 

 
 

Safety information!

 

Expert electricians only may open this device in due compliance with the wiring 
diagram  shown  in  the  housing  cover / on  the  housing / represented  in  the 
corresponding  operating  instructions.  All  expert  electricians  charged  with  the 
execution  of  such  works  must  comply  with  the  relevant  safety  regulations 
currently  operative  and  in  force.  Caution:  The  operation  of  the  controller  in  the 
vicinity of other  devices that  do not comply  with the EMC  directives may  affect 
its  functions.  The  company  charged  with  the  installation  of  the  device  must, 
after  the  completion  of  the  installation  works,  instruct  the  user  of  the  control 
system  into  its  functions  and  in  how  to  operate  it  correctly.  These  operating 
instructions  must  be  kept  at  a  place  that  can  be  accessed  freely  by  the 
operating and/or servicing personnel in charge. 
 

Contents

 

1. 

Application 

2. 

Functional description 

2.1  Control characteristics during operation / neutral zone /  
 

luminous indications 

2.2  Option to select between internal or external sensor-based operation 
2.3  Fan function 
2.4  ON/OFF function 
3. 

Installation / mounting 

3.1  Limitation of the temperature setting range 
4. 

Accessories 

5. 

Technical data 

6. 

Data table with external sensor data (characteristic curve) 

7. 

Wiring diagrams and dimensioned drawings / overview of switch positions 

8. 

Warranty 

 

1. Application

 

The air-conditioning controller desribed in these instructions has been specially 
devised  for  the  control  and  triggering  of  fan  coils,  fan  coil  units  and  other  air-
supported  air  conditioning  systems  used  with  valve-equipped  4-pipe  systems 
(normally  closed  valve  types).  The  device  is  suited  for  use  as  internal  sensor-
equipped  single  room  temperature  controller  or,  in  combination  with  a  remote 
sensor,  as  external  control  device.  Regarding  other  applications  not  to  be 
foreseen  by  the  manufacturer  of  this  device,  the  safety  standards  concerning 
these applications need to be followed and adhered to. Regarding the suitability 
of the device for such applications, please refer to section 8. herein. 
 

2. Functional description

 

The  switching  difference  of  the  controller  comes  to  approx.  0.5K.  The 
calculation  of  the  control  characteristics  specified  hereafter  by  way  of  example 
bases on an expected control deviation of the controlled system of 1K. 
 

2.1 Control characteristics during operation

 

neutral zone / luminous indications 

The neutral zone can be set within a range from 0.5 to 6K (factory setting 2K). It 
corresponds to 2K and begins at the heating switch-off point. If set to 22°C, the 
heating  will  be  set  to  a  temperature  above  22°C  while  operating  in  heating 
mode and down to a temperature below 25°C while operating in cooling mode. 
In  both  heating  and  cooling  mode,  the  switching  difference  comes  to  approx. 
1K.  If  set  to  22°C,  the  heating  switch-off  point  is  thus  at  approx.  23°C  and  the 
cooling switch-off point at approx. 26°C. As long as the heating output is active, 
the  lamp  behind  the  setting  mark  lights  red.  After  deactivation  of  the  heating 
output the fan will continue operating for approx. one minute. The lamp behind 
the setting mark blinks red during this time. Once the cooling output is activated, 
the lamp in the setting mark blinks blue. 

 

2.2 Option to select between internal or external 
sensor-based operation  

The selector switch S2 (see section 7.) enables to set the device for either the 
utilisation of the internal (factory setting) or the external sensor. The terminals  

 
 
 
 
 

12  and  13  have  been  provided  for  the  connection  of  the  external  sensor.  For  a 
selection of suitable sensors, please refer to section 4., "Accessories". 
 

2.3 Fan function

      

The  controller  is  equipped  with  a  3-speed  switch  for  the  selection  of  the  desired 
fan  level.  The  switch  S1  (see  section  7.)  enables  to  set  the  fan  ON  (factory 
setting)  or  OFF  within  the  neutral  zone.  In  order  to  enable  the  internal  sensor  to 
detect the room temperature in an optimal manner, we recommend setting the fan 
in the neutral zone to ON when controlling temperature equalization systems that 
feature  a  fan-assisted  convection  of  the  ambient  air.  The  fan  is  permanently 
activated in this case. If setting the fan to OFF within the neutral zone, it remains 
deactivated across the entire temperature range, i.e. between the switch-off points 
"heating"  and  "cooling"  (=  neutral  zone,  see  diagram  "Switch-points").  The 
triggering  of  the  fan  takes  place  in  a  potential-free  manner,  which  enables  to 
control  fan  motors  with  separated  windings  or  fan  motors  using  a  step  trans-
former. 

Caution: 

No protection class III fans or consumers must be connected! 

 

2.4 ON/OFF function

 

The ON/OFF switch enables to activate or deactivate the control system. 

3. Installation / mounting 

The  device  is,  depending  on  its  size,  either  delivered  in  closed,  or,  in  order  to 
facilitate  its  installation,  in  opened  condition.  After  its  installation,  its  electrical 
connection  and  the  safe  separation  between  mains  voltage  and  safety  extra  low 
voltage  using  the  enclosed  partition  (see  section  7.),  the  housing  cover  needs  to 
be closed by hooking the lower hooks in the housing and folding the cover upward 
until it clicks into place. Following this, the housing cover should be secured using 
the accompanying screw. For opening it, proceed in inverse order to closing. 

Caution:

 When  using  an  external  sensor,  care  must  be  taken  to  ensure  that  the 

sensor  line  is  not  laid  in  parallel  to  line  voltage  carrying  cables  or  lines.  Where 
parallel laying cannot be avoided, a shielded line is to be used and the shielding to 
be  connected  to  the  terminal  13,  15  or  17.  In  order  to  ensure  the  easy 
replacement  of  a  defective  sensor,  the  sensor  including  its  line  needs  to  be  laid 
inside an empty conduit in a replaceable manner. The controller is determined for 
wall mounting or installation on an UP box and must not be exposed to direct heat 
or cold sources. Also care must be taken to ensure that the device is not exposed 
to the influence of foreign heat or cold sources that warm or cool the device at its 
back (through  air flows in cavity  walls  or the temperatures radiated by ascending 
pipelines, f. ex.). 

 

3.1 Limitation of the temperature setting range 

The mobile setting elements underneath of the control knob enable to delimit the 
setting range of the controller mechanically. For this purpose, remove the control 
knob and set  the stops as  required  (red stop for maximum temperature and  blue 
stop for minimum temperature). Once this has been done, the control knob can be 
put on again. 

 

 
 
4. Accessories 

External  temperature  sensor  for  use  in  air  ducts  or  conduits  or  inside  of  rooms: 
LF-2 (cable design air sensor) or HF-2 (sleeve sensor) or GFL-2 (air conduit or air 
duct  sensor  for  direct  installation  at  the  conduit  or  duct)  or  BTF-2  (ambient 
temperature sensor for surface installation).

 

Typ 196000148925

 

 

Electronic Air-conditioning 

Controller 

 

Summary of Contents for 196000148925

Page 1: ... siehe Punkt 4 Zubehör 2 3 Ventilatorfunktion Dieser Regler verfügt über einen 3 stufigen Schalter mit dem die Lüfterstufe gewählt wird Mit dem Schalter S1 vgl Punkt 7 wird die Lüfterfunktion An Werkseinstellung oder Aus in der neutralen Zone eingestellt Um die Raum temperatur mit dem internen Fühler optimal zu erfassen wird bei Temperiersys temen mit lüfterunterstützter Konvektion die Lüfterfunkt...

Page 2: ...L 5012 Ausstattung Schalter Ein Aus Ventilatorschalter 3 stufig mechanische Bereichseinengung des Sollwertstellers innenliegender Schalter zur Auswahl interner Werkseinstellung externer Temperaturfühler innenliegender Schalter zur Auswahl Lüfter an Werkseinstellung aus in der neutralen Zone zweifarbig hinterleuchtete Einstellmarke 6 Fühlertabelle Kennlinie für externe Fühler Die Fühlertabelle gilt...

Page 3: ...switch S2 see section 7 enables to set the device for either the utilisation of the internal factory setting or the external sensor The terminals 12 and 13 have been provided for the connection of the external sensor For a selection of suitable sensors please refer to section 4 Accessories 2 3 Fan function The controller is equipped with a 3 speed switch for the selection of the desired fan level ...

Page 4: ...ch 3 speed fan switch Reference setter with mechanical range limitation Internal switch for selection between internal factory setting external temperature sensor Internal switch for selection between fan ON factory setting or fan OFF within the neutral zone Setting mark backlit two colours 6 Data table with external sensor data characteristic curve The table shown below applies to the optional ex...