background image

 

 

 

15

 

2

 

Building-in instructions 

 
 With the Fera there are two ways of dissipating the convection heat. 

With the standard Fera (Figure 2) convection heat must be dissipated 

by means of grates using a convection set (see Figure 9). The Fera 

Uni (see Figure 3) has a convection box with a “cold” air inlet and a 

warm air outlet. With natural ventilation the “cold” air is sucked out of 

the room, underneath the fire. The air is heated up and leaves the 
Fera at the top. The Fera Design mantle has its own convection 

system. 

  
This is because it is very important that the air cools the fire down. 

Otherwise it reaches excessively high temperatures which can cause 

the  plasterwork or the marble mantel piece to crack. If a Fera Uni is 

installed in combination with a marble mantel piece, then the 
convection grates are often still connected in order to guarantee as 

much cooling as possible. This is also vitally important if you have an 

appliance with radio remote control. The better the cooling, the longer 
the life of the fire.  All appliances are tested and inspected with the 

Uni which does not have convection grates and the standard one 

which does have convection grates. 

 

Figure 3 : Fera Uni 

 

Figure 2 : Fera  

 

 

 

 

16

2.1

 

Choice of material 

The materials used to convert the fire must be heat-resistant and 

fireproof. Under no circumstances must there must be any flammable 
material within the area of the fire. If mounting is carried out using 

materials known in the industry (which have an insulating effect) such 

as for example Promatect, Nobranda and gas concrete blocks, the 

convection set MUST be connected to the appliance, in order to 
effectively convey the heat from the appliance into the room. 

 

2.2

 

The Fera 60, 75 and 105 

 

The Fera’s contents consist of:  

 

 

 

Fera 60/75/105  

 

Installation and operating instructions 

 

White stones/ chips or moulded fire bricks/ Logs (The logs are 
only delivered in combination with the chips). 

 

Adjustable feet. 

 

To gain access to these contents, firstly remove the frame which is 
held fast by magnets. The swinging door can be opened by removing 

the two bolts (the large ones) situated on the right-hand side of the 

fire. With the Fera 105, care must be taken that the appliance does 
not tip forwards when the door is opened. When the swinging door is 

shut again, care must be taken that the bolts are not overtightened, 

otherwise the glass may break. Tight is tight enough. Always check 
the appliance for possible damage and possible faults before installing 

it completely.  

 

2.2.1

 

The connections 

 

The Fera is supplied with a 15mm gas connection as standard. 

This appliance must always be connected to a gas tap which 

can be operated at all times. 

 

If you have a radio remote control, you will require a 230V 

electric socket earthed for safety.  

 

The concentric flue has already been covered in detail in 
Chapter 1 and should be manufactured by Kal-Fire. 

 

Summary of Contents for Fera 105

Page 1: ...ATERIAL 16 2 2 THE FERA 60 75 AND 105 16 2 2 1 THE CONNECTIONS 16 2 2 2 POSITIONING OF THE CHIPS MOULDED FIRE BRICKS WHITE STONES AND LOGS 17 2 2 3 MOUNTING OF THE CONVECTION SET FOR THE FERA 23 2 2 4...

Page 2: ...ADIO 50 6 WARRANTY CERTIFICATE 51 6 1 WARRANTY CONDITIONS 52 6 2 THE WARRANTY IS NOT APPLICABLE IN THE FOLLOWING CASES 53 4 Introduction The closed built in gas fire which you have just purchased from...

Page 3: ...or a supply of fresh air and the flue gases are conveyed directly to the outside via the internal pipe Figure 1 Wall duct with cage 6 1 1 Flue requirements With the Fera you have a choice of two types...

Page 4: ...ed depending on the wall thickness Firstly fit a 1 m piece onto the fire s connection collar fit the 90 bend to this piece and if necessary shorten the wall duct to the desired length and connect it t...

Page 5: ...on air Always check the existing chimney on leakage otherwise the balanced flue system won t work If the existing chimney is in a bad condition we prefer to use two flexible flues The outer flue is fo...

Page 6: ...90 bend upwards The flue then extends for 1 metre upwards to a roof duct 1 metre vertical 1 metre 90 bend 2 metres 0 5 metres horizontal 0 5 1 5 0 75 metres 90 bend 2 metres 1 metre vertical 1 metre R...

Page 7: ...1 C11 C31 Gas P G20 20 mbar G20 20 mbar G25 25 mbar G25 25 mbar G25 20 mbar G20 20 mbar G30 37 mbar Gascat I2L IE2 I2ELL I2H I3P Input output 11 9 kW 4 8 kW 12 6 kW 4 6 kW 10 6 kW 4 8 kW 12 6 kW 4 6 k...

Page 8: ...here must be any flammable material within the area of the fire If mounting is carried out using materials known in the industry which have an insulating effect such as for example Promatect Nobranda...

Page 9: ...ough the chips will produce a thinner chip which will glow more Tip 2 Before putting the chips in place it is best to position the rearmost log first and also the two logs on either side The chips can...

Page 10: ...et of logs is to be positioned as follows Figuur 5 Houtstammetjes Fera 60 1 3 2 4 1 3 4 2 Figure 5 Fera 60 logs 20 For the Fera 75 This is the set of logs you have received The set of logs is to be po...

Page 11: ...t of logs is to be positioned as follows 5 2 6 3 1 4 Figure 7 Fera 75 corner logs 1 2 3 5 4 6 7 11 10 8 9 7 8 9 10 11 22 For the Fera 105 This is the set of logs you have received The set of logs is t...

Page 12: ...ase of installation in a natural stone mantel piece depending on the type of natural stone we still advise using the convection sets so that not all the heat affects the natural stone Figure 9 convect...

Page 13: ...e loosened by means of the screws at the inside and remounted after everything has been finished 10 For putting the front cap back into place wear the supplied white gloves in order to avoid possible...

Page 14: ...rom the stove by lifting it up 2 Carefully take out the Fera appliance from the main frame and put it aside in a safe place 3 Take the main frame from the stove off the pallet and drill a hole in the...

Page 15: ...pliances with manual control ultrasound remote control and radio remote control 3 1 Manually controlled appliances 3 1 1 Lighting the burners Make sure the gas tap is turned on The main burner in the...

Page 16: ...the gas tap is turned on The main burner in the fire is ignited by a pilot light which in turn is ignited by a piezo element Once the pilot light is lit it heats up a thermocouple which creates a sma...

Page 17: ...n the two contacts Plug into the electric socket and turn on the gas tap 3 3 1 Lighting the burners When the Big flame Figure 14 no 1 and the Off knob no 3 are pushed in simultaneously two knob igniti...

Page 18: ...y pressing the ON and OFF knob 3 3 2 Extinguishing the burners To completely extinguish the fire press the OFF knob Figure 14 no 3 on the transmitter and the main burners as well as the pilot light wi...

Page 19: ...37 38...

Page 20: ...39 40...

Page 21: ...41 42...

Page 22: ...43 44 Fera 75 corner RIGHT...

Page 23: ...45 Fera 75 corner LEFT 46...

Page 24: ...continuously Check that the gas tap is turned on or whether there is a blockage in the gas supply The thermocouple is broken Contact your dealer Is the ignition knob turned on fully It must be turned...

Page 25: ...y on Burner bed comes on The Fura burns very blue It needs 30 minutes in order to heat up completely Please contact your dealer about other problems Check that the gas tap is turned on or whether ther...

Page 26: ...ear starting on the date of purchase which must be clearly and distinctly stated on the sales invoice The attached warranty registration card should be carefully completed and returned to Kal Fire B V...

Page 27: ...whatsoever are made to the appliances 4 If the owner of the appliance changes 5 If the appliance is not installed in accordance with the installation instructions and or not used in accordance with th...

Reviews: