➤ For other application conditions, check and determine the supply cross-sections accord‐
ing to DIN VDE 0100 and DIN VDE 0298-4:2013-06 or the local energy provider.
Other application conditions would include, for example:
■ Higher ambient temperature
■ Other cable installation method
■ Other cable bundling
■ Cable length >50 m
Further information Motor voltage tolerances to DIN EN 60034-1.
Rated voltage: 400V / 3 / 50Hz
Compressor type
Backup fuse [A]
Supply line [mm
2
]
Power consumption
1)
[A]
KCT blue 110-24 T
—
—
—
KCT blue 230-24 T
10
4 x 1.5
3.3
KCT blue 230-65 T
10
4 x 1.5
3.3
KCT blue 420-65 T
10
4 x 1.5
5.1
KCT blue 420-90 T
16
4 x 2.5
10.2
1)
power consumption of machine at maximum pressure
Tab. 17 Supply details 400V / 3 / 50Hz
2.12 Network Conditions
The mains conditions apply to machines connected to public mains supplies with the following
characteristics:
■ Mains frequency: 50Hz
■ Rated voltage between exterior and neutral lines 220V ... 250V
■ Rated voltage between the external lines 380V ... 430V
They do not apply to private power supplies within industrial areas isolated from the public
mains.
The machines listed in the table are intended for operation with a public power supply with a
network impedance at the transfer point (house connection) of maximum Z
max.
[Ohm].
The operator must ensure that the machines are only connected to a network that meets these
requirements. If necessary, ask the local electricity utility for the mains conditions.
2.12.1 Supply conditions at 230V / 1 / 50Hz
Compressor model
Maximum permissible motor starts
1)
[1/h]
Highest permissible System impe‐
dance
2)
Z
max.
[Ω]
KCT blue 110-24 T
20
0.339
KCT blue 230-24 T
20
0.132
KCT blue 230-65 T
20
0.132
1)
Exceeding the maximum permissible starts must be discussed with the manufacturer.
2)
The data are relative to the sum of impedances in external and neutral lines.
2
Technical Specifications
2.12 Network Conditions
10
Operator manual Reciprocating compressor
KCT blue T
No.: 902350 00E
Summary of Contents for KCT blue T Series
Page 2: ...Original instructions KKW PDENT 2 10 en SBA DENTAL T ANLAGE 20190503 092636...
Page 6: ...Contents iv Operator manual Reciprocating compressor KCT blue T No 902350 00E...
Page 8: ...List of Illustrations vi Operator manual Reciprocating compressor KCT blue T No 902350 00E...
Page 10: ...List of Tables viii Operator manual Reciprocating compressor KCT blue T No 902350 00E...