Compressor model
Mass [kg]
EPC 440-G
50/100
1)
EPC 630-G
70/130
1)
EPC 840-G
70/130
1)
EPC 1100-G
100/240
1)
EPC 1500-G
130/260
1)
1)
Machine with sound enclosure
Tab. 5 Mass
2.4 Compressor block
Compressor block model
Compressor model
Flow rate
1)
at 6 bar
[l/min]
Number of cylinders
KC 350
EPC 340-G
195
1
KC 400
EPC 440-G
280
2
KC 630
EPC 630-G
410
2
KC 840
EPC 840-G
590
2
KC 1100
EPC 1100-G
750
2
KC 1500
EPC 1500-G
1000
2
1)
Flow rate in accordance with ISO 1217:2009, Annex C
Tab. 6 Compressor block
2.5 Ambient conditions
Installation
Maximum eleva‐
tion AMSL
1)
[m]
1000
Permissible ambient tem‐
perature [°C]
5-35
1)
Higher altitudes are permissible only after consultation with the manufacturer.
Tab. 7 Ambient conditions
2.6 Ventilation
The values given are minimum guide values.
Compressor model
Inlet aperture (Z) [m
2
]
Exhaust fan (A)
1)
[m
3
/h]
EPC 340-G
0.4
510
1)
Forced ventilation: Required air volume for exhaust fan at static compression 1 mbar (machine
in enclosed space without ducts and ΔT≙10 K)
2
Technical Specifications
2.4
Compressor block
No.: 9_5752 24 E
Assembly and operating manual 1-stage piston compressor
EPC-G