8.6.3 Controlling machine from a remote location
If the machine is to be started and stopped from a remote control centre, provide the following set‐
tings:
Overview
■ Make the electrical connection (a spare input for the remote contact is to be found in the elec‐
trical wiring diagram for the machine, DI 1.07 being preferred).
■ Switch machine start to remote mode
■ Activating the «remote control» key
■ If necessary, activate the «Time control» key and configure the clock program (see chap‐
■ If required, assign a different input for the remote contact
RC.
■ Press the «Remote control» key.
8.6.3.1 Switch machine start to remote mode
Two methods are available to start the machine remotely from a control centre:
■ Variant A: Start the machine with the input signal from the remote control centre.
■ Variant B: Starting the machine from the remote control centre in addition to a configured
ON/OFF clock program.
The machine can be started from the remote control centre even though the time control is ac‐
tivated and the ON/OFF program has selected OFF at this point in time.
Precondition The electrical connection has been made.
Access level 2 is activated.
The operating mode is displayed.
1. Open the 5.4.1
<Configuration – Compressor start – Compressor on> menu.
2. Use «Up» or «Down» to select the
Remote mode line.
3. Press the «DOWN» key.
4. Press «Enter».
The currently active operating mode flashes.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.4.1 Compressor on
Menu
Local mode:
Key
Remote mode:
Key
Active line
------------------------------
RC
DI1.07
ok
☑
5. Use «Up» or «Down» to set the
Key + remote contact input.
8
Initial Start-up
8.6
Machine start and machine stop
100
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.0.X
No.: 9_9450 12 E