8.2.
Integration options
The component has two different options for current measurement. The internal
current sensors may be loaded with a maximum of 50 A. The external current
sensors (optional) may be loaded up to a maximum of 100 A. Compensation
control and feed-in limitation in connection with external feeders is possible up to
a maximum of 35 A for internal current sensors and 70 A for external current
sensors.
Only consumers that are installed downstream of the component on the grid
connection side and in the same area of the local installation as the blueplanet
hybrid inverter can be entitled to replacement power (if enabled, see 4.1).
No. Description
1
Power supply company counter (bidirectional meter)
2
blueplanet hy-switch
3
Switchable line protection (4p 20A)
4
EVU counter for generation (optional)
5
RCD type B, 30 mA (required for backup power operation)
6
blueplanet hybrid inverter
7
Load