7
Installation
7.1
Opening the device
↻
The device has been installed on the mount.
↻
Wipe any moisture off the frame of the housing cover using a cloth.
1. Undo the 6 screws (2) and carefully remove the housing cover (1) [ T_25]
2. Be careful not to damage or soil the seals or optical fibers when setting the
housing cover down.
ð
Proceed with the installation of the device.
2
1
Fig. 15:
Removing the housing
cover
7.2
Surveying the connection area
The connection point for the AC supply is situated inside the housing. The DC input source is also connected in-
side the housing.
3
2
1
Fig. 16:
Connection area M-Version
3
4
2
1
Fig. 17:
Connection area L-Version
3
4
2
1
Fig. 18:
Connection area XL-Version
Legende
1
AC connection point
3
DC fuse with connection point
2
DC connection point
4
DC load relay(for precharge unit)
7.3
Making the electrical connections
NOTE
Select conductor cross-section, safety type and safety value in accordance with the following basic
conditions:
Country-specific installation standards; power rating of the device; cable length; type of cable installation; local
temperature
NOTE
Due to the fact that the device is unable to limit the short circuit current from the grid in the event of a short
circuit, the AC-side fuse in the installation (on-site) provides protection against faults on the DC side.
For device safety, the max. prospective DC current is limited by the internal DC fuse in the event of an error.
Specification of the DC fuse (F1):
• 250Adc nominal current
• Nominal voltage (DC) > max. battery voltage
• Breaking capacity: 30kA
Use of e.g. Bussmann EATON PV-250A-2XL-3BU-15 (1500Vdc).
Manual
Installation | 7
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
Page 21
EN-US