1
P [p.u.]
Q [P.u]
0,6
0,4
0,2
0
1
0,8
1,2
0,6
0,6
1
0,0
above U
N
at 0,9 U
N
at 0,8 U
N
underexcited
overexcited
Fig. 64:
P-Q operating range for bp 125 TL3 (Q
max
=S
max
)
760
S [p.u. S
nom
]
U [V]
0,6
0,4
0,2
0
1
0,8
1,2
560
680
520
480
600
640
720
Over load capability
Nominal capability
Under voltage
derating
U
V
R
T
O
V
R
T
Fig. 65:
Apparent power subject to the grid voltage bp
125TL3
1
P [p.u.]
Q [P.u]
0,6
0,4
0,2
0
1
0,8
1,2
0,6
0,6
1
0,0
above U
N
at 0,9 U
N
at 0,8 U
N
underexcited
overexcited
Fig. 66:
P-Q operating range for bp 110 TL3 (Q
max
=S
max
)
580
S [p.u. S
nom
]
U [V]
0,6
0,4
0,2
0
1
0,8
1,2
380
500
340
300
420
460
540
Nominal capability
O
V
R
T
Under voltage
derating
U
V
R
T
Fig. 67:
Apparent power subject to the grid voltage bp
110TL3
1
P [p.u.]
Q [P.u]
0,6
0,4
0,2
0
1
0,8
1,2
0,6
0,6
1
0,0
above U
N
at 0,9 U
N
at 0,8 U
N
underexcited
overexcited
Fig. 68:
P-Q operating range for blueplanet 92.0TL3
(Q
max
=S
max
)
580
S [p.u. S
nom
]
U [V]
0,6
0,4
0,2
0
1
0,8
1,2
380
500
340
300
420
460
540
Nominal capability
O
V
R
T
U
V
R
T
Under voltage
derating
Fig. 69:
Apparent power subject to the grid voltage bp
92.0TL3
1
P [p.u.]
Q [P.u]
0,6
0,4
0,2
0
1
0,8
1,2
0,6
0,6
1
0,0
above U
N
at 0,9 U
N
at 0,8 U
N
underexcited
overexcited
Fig. 70:
P-Q operating range for blueplanet 87.0TL3
(Qmax=Smax)
580
S [p.u. S
nom
]
U [V]
0,6
0,4
0,2
0
1
0,8
1,2
380
500
340
300
420
460
540
Nominal capability
O
V
R
T
U
V
R
T
Under voltage
derating
Fig. 71:
Apparent power subject to the grid voltage bp
87.0TL3
10.2
Reactive power control
Reactive power can be used in electrical energy supply networks to bolster the level of voltage. As such, feed-in inverters
can contribute to statistical voltage stability. Reactive power brings about a voltage drop at the inductive and capacitive
components of the equipment which can either bolster or reduce the level of voltage. If the generating plant draws induc-
tive reactive power while active power is being fed in, part of the voltage swing caused by the active power feed can be
compensated for by the supply of reactive power.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Page 71