Page 39
KACO blueplanet 3.0 NX3 M2 KACO blueplanet 5.0 NX3 M2 KACO blueplanet 8.0 NX3 M2 KACO blueplanet 10.0 NX3 M2
KACO blueplanet 15.0 NX3 M2 KACO blueplanet 20.0 NX3 M2
9.9.2
Authorisation to change parameters
<Live values and settings> menu has
been opened from <Available
communication units> and <Find inverter>.
1.
Open <Parameter settings> to set the
parameters for initial start-up.
Important: No
password
is required for
initial parameter setting
.
A password must be entered if it
becomes necessary to change the
parameters of the device after initial
start-up (security function). The specific
password for the inverter must be
requested from KACO Service.
2. Enter the password in the
<Password> field and confirm with
<Confirm>.
Fig. 79.
Warning issued only on the
first
accidental abort attempt.
Fig. 80.
Select parameter settings
Fig. 81.
Authorisation required
9.9.3
Selecting country and grid type
The required device is selected in
<Available inverters> and the <Settings
for> menu is opened in the <Parameter
settings> in the <Inverter values &
settings> menu.
1. Select <Country / Grid>.
Caution:
The following settings can only be
made once without a password during
initial start-up!
2. Select the operator country and
grid
type
in
the field according to the
grid
operator requirements
and confirm with
<O.K.>.
Note:
By default, all required parameters
are activated via the relevant grid code.
Note:
When the grid standard has been
changed, the device carries out a self-test.
As a result, around 2 minutes may elapse
before the device feeds in again.
Note:
Further grid standards settings can
be made if requested by the grid operator
or customer (e.g. setting for reactive
power, Q(U) curve, see Chapter 9.13.1).
Fig. 82.
Check or change country
and grid-type
Fig. 83.
Select country & grid code