Connecting remote signal monitoring
↻
It has been ensured that there is no AC/DC voltage present.
↻
Housing cover open.
1. Loosen the cable fitting to pass the signal cable through [ W_20]
2. Replace the sealing insert in the cable fitting with a multiple sealing insert.
3. Feed the remote signal monitoring signal cable through the cable gland and into
the housing.
NOTE: Refer to the technical details on connecting remote signal monit-
oring!
1. Connect the signal cable to the connection terminal of the DC overvoltage pro-
tection in accordance with the terminal allocation [ S_3,5 / 0.25 Nm]
2. Lay the signal cable correctly and tighten the cable fitting [ W_20 / 1.5 Nm]
ð
Remote signal monitoring connected. Proceed with the installation of the
device.
12
14
11
?
1
2
3
Fig. 26:
Connecting overvoltage protec-
tion with remote signal monitoring
1 Terminal block 1 [11,12,14]
3 Terminal block 2 [11,12,14]
5 Multiple sealing insert
Technical data for:
Connecting remote signal monitoring
Operating voltage (AC) / operating voltage (DC)
5 - 250 V / 30 V
Operating current (AC
3
) / operating current (DC)
5mA – 1.5 A / 1 A
Type of connection
Screw connection
Screw thread
M2
Tightening torque
0.25 Nm
Length of insulation to be stripped off
7 mm
Cable cross-section [flexible / rigid]
0.14 – 1.5 mm²
Conductor cross-section
28 – 16 AWG
Terminal allocation
11, 12 [normally closed contact]
11, 14 [normally open contact]
7.7
Creating equipotential bonding
↻
The device has been installed on the mount.
1. Undo the cable fitting for housing ground connection [ W_20]
2. Insert the cable for equipotential bonding through the cable fitting provided
into the connection area.
3. Strip the insulation from the equipotential bonding cable.
4. Furnish the stripped cable with an M4 ring cable lug.
5. Lay the equipotential bonding cable onto the grounding point and attach with
the M4 x 10 bolt and lock washer provided [ W_T30/ 2.2 Nm].
6. Check that the connected cable is fitted securely.
7. Tighten the cable fitting for the housing ground connection [ W_20 / 1.5
Nm].
ð
The housing is included in the equipotential bonding.
1
Fig. 27:
Earthing point
1 Earthing bolt
3
There must be a current of >5mA at all times to act as corrosion protection in order to use the evaluation con-
tact.
Manual
Installation | 7
KACO blueplanet 15.0TL3 KACO blueplanet 20.0TL3
Page 27
EN