operator’s manual 

full of energy 

Summary of Contents for blue planet PVI 1501i

Page 1: ...We reserve the right to technical alterations operator s manual full of energy...

Page 2: ...ting it into operation Warning symbols used in this manual To ensure optimal use of your Blue Planet PVI inverter please take note of the explanations of the following symbols used in this manual This...

Page 3: ...ion 5 2 1 Starting up the inverter 5 2 2 Switching off the inverter 6 2 3 Display Operation and Settings 7 2 4 Setting the Date and Hour 12 2 5 Communication interface setup 13 2 6 Operation of the RS...

Page 4: ...panel Input voltage range 125 to 400 VDC MPP range 125 400VDC RS232 interface as a standard VDEW conformance Optional remote Internet monitoring LCD display showing the following operational data perm...

Page 5: ...essage Start at 130V measurement xxxV If the measured voltage is greater than 130V the device will start grid feeding after approx 4 minutes This startup period of 4 minutes is necessary to ensure tha...

Page 6: ...off the AC disconnect Attention Lethal Hazard Hazardous Live Voltage can be present in the inverter even if the electrical connections have been switched off Please wait for 10 minutes before accessi...

Page 7: ...elivered power The following values and data may appear on the display No Display message Explanation 1 Display shown during the starting up period in the morning after a malfunction or prior to night...

Page 8: ...nd the system is re started after a failure Waiting for night shutdown The generator capacity is no longer sufficient for grid feeding and the device waits for the night shutdown The connected solar g...

Page 9: ...January 1 to date 10 Power delivered since the time of inverter startup 11 Today s operating hours since sunrise Displayed in hours and minutes 12 Operating hours during the past calendar year Januar...

Page 10: ...to re entry date and hour Fig 1 Start button Please note The displayed measuring values i e generator current generator voltage grid current grid voltage etc all have a certain tolerance This will of...

Page 11: ...cess To this effect the generator voltage must first exceed a value of 130 V for 3 4 minutes ensuring that the PV generator provides enough power This means that the Grid Feeding LED is not lit up unl...

Page 12: ...data Key 2 Unique output of internal inverter data for diagnostic purposes via serial interface 2 Output of operating data Output of operating data via the serial interface Standard setting Active 3...

Page 13: ...key to select RS232 or RS485 communication standard is RS232 Press Display again to enter the RS485 address The address is adjustable in the range from 0 to 31 by pressing the Set key standard is add...

Page 14: ...male 9 pole 2 TXD 2 3 RXD 3 4 RTS 4 5 GND 5 Interface parameters Baud rate 9600 baud Data bits 8 Parity None Stop bits 1 Protocol None Below are a few example rows of data transmission Column 1 2 3 4...

Page 15: ...imes of high insolation maximum yield is ensured by means of a patented MPP tracker 9 Troubleshooting operation Initiated whenever an internal error occurs 10 High temperature cut off The inverter is...

Page 16: ...types of operating systems or by using the KACOViso visualization tool The KACOViso program is available for free download from http www kaco geraetetechnik de 2 7 Visualization with KACOViso KacoVis...

Page 17: ...aphs The selection of the type of graph is user specific and can be combined in any desired way For example a daily yield curve can be displayed as a 2D bar graph or as a 3D area chart showing the tem...

Page 18: ...Electrical Data Rated power 1500W Max power 1800W short term Grid voltage 190 264 V Rated current 6 5 A Max current 7 8 A Power factor 1 Frequency 50Hz 1 Distortion factor according to VDE0383 3 at r...

Page 19: ...otection Class of the device 1 Basic insulation PE connection Protection Class of connected modules 2 VDEW Conformance VDEW Association of German Power Generating Plants According to the regulations o...

Page 20: ...ter continues to work properly and without any yield losses Values are reset overnight If you wish to reset the display immediately disconnect the inverter and the DC grid voltage supply and switch on...

Page 21: ...operation Grid failures may cause interruptions during the day If more than 10 interruptions should occur over several weeks you should contact your solar installation provider The inverter does not...

Page 22: ...eries 3 Number of strings 4 Generator power If it should become necessary to return the PVI for repair please use the original packaging 4 2 Transport damage To ensure high quality and reliability Blu...

Page 23: ...t PVI KACO GER TETECHNIK GmbH 23 operator s manual AU Your solar installation provider Our product range INVERTERS FREQUENCY CONVERTERS DC DC CONVERTERS CHARGE RECTIFIERS POWER SUPPLIES FUSED DC VOLTA...