Programming Reference
1.6 Scale menu
Page 30
Docu-No.: 0590020601-EN Rev. 1.6.0
1.6
Scale menu
This menu programs the scale parameters and SFT operation in two
separate menus/screens.
1.6.1
General sub-menu
Parameter
Definition
TARE
Tare Weight
Weight of the feeder with no material. This value will set
automatically when Auto Tare function is executed.
Input range: 0 to scale range [kg]
AUTO TARE
This command allows the current weight value to be entered into the
TARE memory when the product hopper is empty.
For KSU-II/KCM select parameter then press
For KSL press
F5-MORE
then
For KSC press
SPAN
Weight Span
Input of the span correction factor for fine compensation of
mechanical scale weighing errors. This value may automatically
change if the Auto Span feature is used in the CALIBRATION menu.
Input range: 0.4 to 2.5
Default: 1.000
NET WEIGHT
Net Weight
Display of the current weight of the feeding material on the scale.
Net weight = Gross Weight - Tare
Range: Display only 0 to scale range [kg]
GROSS WT
Gross Weight
Display of the current total weight of the feeder and feeding material
on the scale.
Range: Display only, 0 to scale range [kg]
SCALE RANGE
Scale Range
Input of the scale's nominal capacity.This value will be read
automatically from the connected load cell (s). If an mechanical
reduction is used (e.g. B3 weighing bridges) enter the new weighing
range with the service variable Scale Range.
Range: read only