Docu-No.: 0590020601-EN Rev. 1.6.0
Page 23
Programming Reference
1
Alarm menu 1.3
1.3.2
Alarm setup sub-menu
Parameter
Definition
ALARM DELAY [sec]
Alarm Delay
Time between the alarm detection and activation of the alarm relay
output when the alarm is of the type <Timed> or <Timed-Stop>. The
alarm output will not be activated and the alarm will be cancelled if
the fault is corrected within this time period.
Input range: 0 to 999 seconds Default: 30 seconds.
STARTUP DELAY [sec]
Startup Delay
Time during which process related alarm signals are suppressed
when the machine is being started up. See section
.
e.g. Massflow High error is suppressed.
Input range: 0 to 999 seconds Default: 60 seconds.
STOP CLRS ALARM
Clear Alarm on Stops
Select <Yes> if alarms are to be cleared when a stop occurs. Select
<No> if alarms are not to be cleared during a Stop action.
Default: No
ALR
Number of Selected
Alarm
Input of the alarm number, which can be selected from the list in the
appendix. With the programming variable ALARM MODE the
selected alarm number can be influenced.
Input range: See section
ALR
Name of Selected Alarm
Shows the alarm function for the selected alarm number.
ALARM MODE
Selected Alarm Mode
The selected alarm at the variable Alarm number can be influenced
as follows:
Setting
Definition
IGNORE
Alarm will be ignored.
IMMED
Alarm will be activated immediately but ALS output
will not change.
IMMED-STOP
Alarm will be activated immediately and ALS
output switches ON.
TIMED
Alarm will be activated after entered startup up-
and alarm delays but ALS output will not change.
TIMED-STOP
Alarm will be activated after entered startup and
alarm delays and ALS output switches ON.
Selection will depend upon the action desired.
Table page 1 of 2