5.2.5. Scene function object of “Switch actuator"
Fig. 5.2.5 Scene function communication object of “Switch Actuator”
No.
Function
Object name
Data type
Flags
DPT
14
Scene
Output A-{{...}}
1Byte
C,W
18.001 scene control
It is able to recall or save the scene when sending an 8-bit command by this object, which will be
enabled when enabling the scene function. The definition of the 8-bit command will be described
below:
Assuming an 8-bit command (binary coding) as: FXNNNNNN
F: recall the scene with “0”; save the scene with “1”;
X: 0
NNNNNN: scene number (1-64).
1-64 in the parameter setup corresponds to the scene number 0-63 received by the
communication object “Scene handle”. For example, scene 1 in the parameter setup has the same
output result as scene 0 in the communication object “Scene handle”.
Table 5.2.5 Scene function communication object “Switch Actuator”
5.2.6. Threshold function object of “Switch actuator”
Fig. 5.2.6 Threshold function communication object “Switch Actuator”
No.
Function
Object name
Data type Flags
DPT
15
Change threshold 1
Output A-{{...}} 1Byte
C,W
5.010 counter pulses
This object is used to change the value of the threshold 1.
16
Threshold input
Output A-{{...}} 1Byte
C,W
5.010 counter pulses
This object is used to receive the threshold sent by other devices.