Bus Revision 42
FPGA Revision 1
To check the status of a specific SCB, issue the show chassis environment cb node slot command, for
example, show chassis environment cb node 0.
For more information about using the CLI, see the
.
Taking the SRX5800 Services Gateway Host Subsystem Offline
The host subsystem is composed of an SCB with a Routing Engine installed in it. You take the host subsystem
offline and bring it online as a unit. Before you replace an SCB or a Routing Engine, you must take the host
subsystem offline. Taking the host subsystem offline causes the device to shut down.
To take the host subsystem offline:
1. On the console or other management device connected to the Routing Engine that is paired with the
SCB you are removing, enter CLI operational mode and issue the following command. The command
shuts down the Routing Engine cleanly, so its state information is preserved:
user@host>
request system halt
2. Wait until a message appears on the console confirming that the operating system has halted.
For more information about the command, see Junos OS System Basics and Services Command Reference
at
www.juniper.net/documentation/
NOTE:
The SCB might continue forwarding traffic for approximately 5 minutes after the
request system halt command has been issued.
Operating and Positioning the SRX5800 Services Gateway SCB Ejectors
•
When removing or inserting an SCB, ensure that the SCBs or blank panels in adjacent slots are fully
inserted to avoid hitting them with the ejector handles. The ejector handles require that all adjacent
components be completely inserted so the ejector handles do not hit them, which could result in damage.
•
The ejector handles have a center of rotation and need to be stored toward the center of the board.
Ensure the long ends of the ejectors located at both the top and the bottom of the board are vertical
306
Summary of Contents for SRX 5800
Page 1: ...SRX5800 Services Gateway Hardware Guide Published 2020 02 10 ...
Page 23: ......
Page 30: ...Figure 2 Rear View of a Fully Configured AC Powered Services Gateway Chassis 31 ...
Page 111: ...LEDs 112 ...
Page 121: ...Port and Interface Numbering 122 ...
Page 127: ...Port and Interface Numbering 128 ...
Page 161: ......
Page 179: ... One SRX5K MPC IOC2 Modular Port Concentrator with two Modular Interface Cards MICs 180 ...
Page 180: ... One SRX5K 40GE SFP I O card IOC 181 ...
Page 205: ......
Page 261: ......
Page 324: ...c Upload the configuration to RE2 from the USB device 325 ...
Page 365: ...Figure 143 Installing an SPC 366 ...
Page 367: ...368 ...
Page 422: ...5 CHAPTER Troubleshooting Hardware Troubleshooting the SRX5800 425 ...
Page 423: ......
Page 457: ......
Page 473: ...475 ...
Page 476: ...Restricted Access Area Warning 478 ...
Page 483: ...485 ...
Page 496: ...Jewelry Removal Warning 498 ...
Page 499: ...Operating Temperature Warning 501 ...
Page 509: ...DC Power Disconnection Warning 511 ...
Page 513: ...DC Power Wiring Sequence Warning 515 ...
Page 516: ...DC Power Wiring Terminations Warning 518 ...
Page 519: ...DC Power Disconnection Warning 521 ...
Page 523: ...DC Power Wiring Sequence Warning 525 ...