3.
Reinstalling Cards After Installing the SRX5800 Services Gateway Chassis | 229
4.
Reinstalling the Cable Manager After Installing the SRX5800 Services Gateway Chassis | 231
Reinstalling Power Supplies After Installing the SRX5800 Services Gateway Chassis
Reinstall the rightmost power supply first and then work your way to the left. To reinstall the AC or DC
power supplies, follow this procedure for each power supply (see
, which shows the
installation of the DC power supplies):
1. Attach an ESD grounding strap to your bare wrist, and connect the strap to one of the ESD points on
the chassis.
Verify that the power supplies are switched off:
•
For an AC-powered services gateway, verify that the AC input switch on the chassis above each AC
power supply is in the off (O) position. If the services gateway is equipped with high-capacity AC
power supplies, also verify that the AC input switch on each power supply is in the off (O) position.
•
For DC-powered services gateway, verify that the DC circuit breaker on each power supply faceplate
is in the off (O) position.
We recommend verifying that the power supplies are switched off even though they are not connected
to power sources.
2. Ensure that the release lever below the empty power supply slot is locked in the counterclockwise
position (see
If necessary, pull the spring-loaded locking pin in the release lever away from the chassis and turn the
release lever counterclockwise until it stops. Let go of the locking pin in the release lever. Ensure that
the pin is seated inside the corresponding hole in the chassis.
3. Using both hands, slide the power supply straight into the chassis until the power supply is fully seated
in the chassis slot. The power supply faceplate should be flush with any adjacent power supply faceplates.
The small tab on the metal housing that is controlled by the release lever must be inside of the
corresponding slot at the bottom of the power supply. This tab is used to pull the power supply down
in the chassis slot, prior to removing the power supply.
4. While firmly pushing the handle on the power supply faceplate with one hand, use your other hand to
pull the spring-loaded locking pin in the release lever away from the chassis and turn the release lever
clockwise until it stops.
5. Let go of the locking pin in the release lever. Ensure that the pin is seated inside the corresponding
hole in the chassis.
226
Summary of Contents for SRX 5800
Page 1: ...SRX5800 Services Gateway Hardware Guide Published 2020 02 10 ...
Page 23: ......
Page 30: ...Figure 2 Rear View of a Fully Configured AC Powered Services Gateway Chassis 31 ...
Page 111: ...LEDs 112 ...
Page 121: ...Port and Interface Numbering 122 ...
Page 127: ...Port and Interface Numbering 128 ...
Page 161: ......
Page 179: ... One SRX5K MPC IOC2 Modular Port Concentrator with two Modular Interface Cards MICs 180 ...
Page 180: ... One SRX5K 40GE SFP I O card IOC 181 ...
Page 205: ......
Page 261: ......
Page 324: ...c Upload the configuration to RE2 from the USB device 325 ...
Page 365: ...Figure 143 Installing an SPC 366 ...
Page 367: ...368 ...
Page 422: ...5 CHAPTER Troubleshooting Hardware Troubleshooting the SRX5800 425 ...
Page 423: ......
Page 457: ......
Page 473: ...475 ...
Page 476: ...Restricted Access Area Warning 478 ...
Page 483: ...485 ...
Page 496: ...Jewelry Removal Warning 498 ...
Page 499: ...Operating Temperature Warning 501 ...
Page 509: ...DC Power Disconnection Warning 511 ...
Page 513: ...DC Power Wiring Sequence Warning 515 ...
Page 516: ...DC Power Wiring Terminations Warning 518 ...
Page 519: ...DC Power Disconnection Warning 521 ...
Page 523: ...DC Power Wiring Sequence Warning 525 ...