state indicates that the link between the SIB and FPC has CRC errors. However, the link is still
eligible to carry traffic.
•
show chassis fabric sibs
—Check the switch fabric links between the SIBs and FPCs. The value of
the
Fabric management SIB state
field in the command output should be
Links ok
. The
Link error
state
indicates that the link between the SIB and the FPC is not operational.
TIP: If there are errors, the
show chassis fabric topology
command shows more details about
the current fabric plane and link state. See
"Troubleshooting the PTX5000 Switch Interface
for more information.
3.
Reset the interface statistics by using the
clear interfaces statistics all
command so that you can
easily determine whether any traffic drops are occurring during the procedure. Use the
show
interfaces statistics
command to determine whether there are any errors.
4.
Include the
fabric upgrade-mode default
statement in the configuration of the PTX5000 at the
[edit
chassis]
hierarchy level.
[edit]
user@host# set chassis fabric upgrade-mode default
5.
Commit the configuration on both the primary and the backup Routing Engines.
[edit]
user@host# commit synchronize
6.
Use the
show configuration chassis
operational-mode command to verify that upgrade mode is set.
7.
Place an electrostatic bag or antistatic mat on a flat, stable surface.
8.
To prevent damage to the equipment caused by static discharge, attach an ESD grounding strap to
your bare wrist, and connect the strap to one of the ESD points on the chassis.
9.
Take one of the old SIBs offline by using the
request chassis sib offline slot
slot-number
command.
Leave the remaining SIBs online.
10. Remove the offline SIB:
a. Twist the ejector handles counterclockwise to unseat the SIB.
548
Summary of Contents for PTX5000
Page 1: ...PTX5000 Packet Transport Router Hardware Guide Published 2022 12 04...
Page 59: ...NOTE The PDUs contain no fans but are cooled by the fans in the power supply modules 41...
Page 63: ...NOTE The PDUs contain no fans but are cooled by the fans in the power supply modules 45...
Page 77: ...High Capacity Delta AC PDU LEDs 66 High Capacity Wye AC PDU 68 59...
Page 78: ...Three Phase Delta AC PDU LEDs Figure 29 on page 61 shows the three phase delta AC PDU LEDs 60...
Page 81: ...Three Phase Wye AC PDU LEDs Figure 30 on page 64 shows the three phase wye AC PDU LEDs 63...
Page 228: ...2 Remove each bracket Figure 81 Removing the Center Mounting Bracket 210...
Page 234: ...8 Move the lift away from the rack 216...
Page 235: ...Figure 83 Loading the PTX5000 onto the Lift 217...
Page 270: ...Figure 119 Connecting 20 A Inputs to a High Capacity Single Phase AC PDU 252...
Page 304: ...Figure 140 Installing the Front Door on a PTX5000 in a Four Post Rack 1 Side panels 2 Door 286...
Page 349: ...6 Discard the air filter Figure 154 Removing a Horizontal Air Filter Tray 331...
Page 352: ...Figure 157 Installing the Horizontal Air Filter 334...
Page 354: ...6 Discard the air filter Figure 158 Removing a Vertical Air Filter Tray 336...
Page 357: ...Figure 161 Installing a Vertical Air Filter Tray 339...
Page 428: ...Figure 216 Connecting 20 A Inputs to High Capacity Single Phase AC PDU 410...
Page 429: ...Figure 217 Connecting 30 A inputs to High Capacity Single Phase AC PDU 411...
Page 447: ...8 Insert the input power tray into the PDU Figure 228 Installing a 60 A Input Power Tray 429...
Page 448: ...Figure 229 60 A DC Input Power Terminals 430...
Page 531: ...Figure 276 Do Not Carry an FPC with Only One Hand 513...
Page 584: ...5 CHAPTER Troubleshooting Hardware Troubleshooting PTX5000 Components 567...
Page 651: ...6 CHAPTER Returning the Chassis or Components Returning the PTX5000 Chassis or Components 634...
Page 662: ...Figure 303 FPC2 PTX P1A Serial Number Label 644...
Page 663: ...Figure 304 FPC3 PTX U2 and FPC3 PTX U3 Serial Number Label 645...
Page 669: ...Figure 309 DC PDU Serial Number Label 651...
Page 670: ...Figure 310 AC PDU Serial Number Label 652...