Check the LED on the SFB faceplate.
During normal operations:
•
The bicolor OK/FAIL LED on the SFB faceplate is lit green steadily.
•
The bicolor OK/FAIL LED on the SFB faceplate is blinking green.
•
The bicolor OK/FAIL red LED on the SFB faceplate is off.
•
Issue the show chassis sfb command to display information about the SFBs. The output is similar to the
following:
user@host>
show chassis sfb
Slot State Uptime
0 Online 2 days, 12 hours, 55 minutes, 20 seconds
1 Online 2 days, 12 hours, 55 minutes, 9 seconds
2 Online 2 days, 12 hours, 54 minutes, 58 seconds
3 Online 2 days, 12 hours, 54 minutes, 47 seconds
4 Online 2 days, 12 hours, 54 minutes, 36 seconds
5 Online 2 days, 12 hours, 54 minutes, 25 seconds
6 Online 2 days, 12 hours, 54 minutes, 15 seconds
7 Online 2 days, 12 hours, 54 minutes, 4 seconds
For further description of the command output, see the
Junos OS System Basics and Services Command
RELATED DOCUMENTATION
Maintaining the MX2010 Switch Processor Mezzanine Board (SPMB)
Purpose
For optimum router performance, verify the switch processor mezzanine board (SPMB) status.
Action
On a regular basis:
681
Summary of Contents for MX2010
Page 1: ...MX2010 Universal Routing Platform Hardware Guide Published 2019 12 03...
Page 28: ......
Page 30: ...MX2010 Power System Description 95 MX2010 Cooling System Description 45 4...
Page 144: ...MX2010 DC Power 48 V System Electrical Specifications 201 122...
Page 146: ......
Page 233: ......
Page 273: ...Figure 98 Loading the MX2010 Router into the Rack g007436 256...
Page 294: ...Figure 113 Reinstalling an AC Power Distribution Module g007440 D 277...
Page 295: ...Figure 114 Reinstalling a DC Power Distribution Module 48 V D g007432 278...
Page 373: ...4 PART Installing and Replacing Components Installing Components 359 Replacing Components 429...
Page 374: ......
Page 620: ......
Page 715: ...6 PART Troubleshooting Hardware Troubleshooting Components 703...
Page 716: ......
Page 744: ......
Page 772: ......
Page 775: ...763...
Page 783: ...772...
Page 796: ...Jewelry Removal Warning 787...
Page 799: ...Operating Temperature Warning 790...
Page 808: ...DC Power Disconnection Warning 799...
Page 812: ...DC Power Wiring Sequence Warning 803...