Heating actuator 6-gang 

Heating actuator 6-gang 

Art.-No.: 2136 REG HZ

Operating instructions 

1 Safety instructions 

Electrical equipment may only be installed and fitted by electrically skilled persons. 

Failure to observe the instructions may cause damage to the device and result in fire and 
other hazards. 

Danger of electric shock. Always disconnect before carrying out work on the devise or 
load. At the same time, take into account all circuit breakers that supply dangerous 
voltage to the device or load. 

Danger of electric shock. Device is not suitable for disconnection from supply voltage. 
The load is not electrically isolated from the mains even when the device is switched off. 

These instructions are an integral part of the product, and must remain with the end 
customer. 

2 Device components 

Figure 1 

(1)  Connection of electrothermal actuators  
(2)  Programming LED 
(3)  Programming button 
(4)  KNX connection 
(5)  Mains voltage connection 

3 Function 

System information 

This device is a product of the KNX system and complies with the KNX directives. Detailed 
technical knowledge obtained in KNX training courses is a prerequisite to proper 
understanding.  
The function of this device depends upon the software. Detailed information on loadable 
software and attainable functionality as well as the software itself can be obtained from the 
manufacturer´s product database. Planning, installation and commissioning of the device are 

1/5 

82543713 
J:0082543713 

20.12.2011 

Summary of Contents for KNX 2136 REG HZ

Page 1: ...ed from the mains even when the device is switched off These instructions are an integral part of the product and must remain with the end customer 2 Device components Figure 1 1 Connection of electrothermal actuators 2 Programming LED 3 Programming button 4 KNX connection 5 Mains voltage connection 3 Function System information This device is a product of the KNX system and complies with the KNX ...

Page 2: ... and connected actuators in case of overload the device determines which output is involved and switches it off Non overloaded outputs continue to work which means that the rooms in question are still heated In case of major overloads the actuator initially switches all off the outputs A1 A6 off In the case of more minor overloads the actuators switches output groups A1 A3 and or A4 A6 off The act...

Page 3: ...t the neutral conductor from the output terminals through to additional devices Do not connect any inductive or capacitive loads o Connect the outputs according to connection diagram figure 2 o Connect the mains voltage figure 2 o Connect bus cable with connecting terminal Installing the cover It is necessary to install a cover to protect the bus connection against hazardous voltages in the connec...

Page 4: ... frequency 50 60 Hz Power loss approx 2 W Ambient conditions Ambient temperature 5 45 C Storage transport temperature 25 70 C Heating outputs Contact type Semi conductor Triac ε Switching voltage AC 230 V 240 V Switching current 5 50 mA Switch on current max 1 5 A 2 sec Number of drives per output max 4 Housing Fitting width 72 mm 4 modules Connection of outputs Connection mode Screw terminal Sing...

Page 5: ... typically lasts 6 20 minutes i After resetting of the overload switch off it is no longer possible for the device to determine which output is overloaded If the cause is not eliminated overload switch off will occur again 5 3 Accessories Connection cover Art No 2050 K 5 4 Warranty We reserve the right to make technical and formal changes to the product in the interest of technical progress We pro...