Connect the KNX line to the red and black bus terminal (8). 

Connect the IP side with RJ45 connector plugged into RJ socket (6). 

picture 3 

Connection example (picture 3). 

4.2 Commissioning 

Loading the physical address and application software 

Use as a data interface: physical address x.y.z.  
Use commissioning software from ETS2 version 1.2 onwards. 

When ETS3 is used, install the additional KNXnet/IP driver. Downloading into the local 
device is not supported at present. 

Press the programming button (9). 
The programming LED (10) is illuminated. 

Assign physical address. 
The programming LED (10) is extinguished. 

Note the physical address on the device label (11). 

Download application software, parameters, etc.  

The IP address is loaded into the device as a parameter together with the application 
software or is automatically assigned by a DHCP service. If no DHCP service is present, 
the device searches for its own IP address (AutoIP).  

In the event of questions about IP address assignment, etc., please consult the local 
network administrator. 

Assigning additional physical addresses 

Additional physical addresses can be assigned manually with ETS or automatically by the 
device itself. 

Press the programming button (9) for approx. 5 seconds. 
The programming LED flashes. 
The device checks the physical addresses present in the line and selects the required free 
physical addresses. 

Determine the physical addresses occupied by the device and insert them in the ETS 
project as dummy devices. 