Jung FST1240EB Operating Instructions Download Page 2

The range of the system can be optimised by selecting the optimal installation location, taking
into account the structural circumstances.

Figure 2: Reduced range due to structural obstacles

Example of penetration of various materials:

Material

Penetration

Wood, Plaster, Plasterboard

approx. 90%

Brick, Chipboard

approx. 70%

Reinforced concrete

approx. 30%

Metal, Metal grid

approx. 10%

Rain, Snow

approx. 1-40%

Intended use

-

Radio-controlled switching and brightness setting for lamp operating devices with 1-10 V
interface

-

Installation in false ceilings or surface mounting

-

Operation with suitable radio transmitters

i

It is not possible to teach a combination of presence detector and motion detector.

Product characteristics

-

Switch-on brightness can be saved permanently

-

Switch-on via bulb-preserving soft start

-

Light scene operation possible

-

Constant light regulation possible in connection with a radio presence detector 

-

Run-on time of approx. 1 minute in connection with radio motion detectors 

4 Operation

A radio transmitter has to be taught in order to be able to operate the device.

i

Observe the instructions for the radio transmitter.

2/5

32532333
J0032532333

08.09.2016

Radio Management 

Radio push-button controller, built-in