Operating Manual: FRWM-IP-GATE - IP-Gateway
43
EN
f
Press gateway button (B) until a
longer acoustic signal is emitted,
then release.
(B)
5
Network reset has been performed.
If the long tone does not sound, see
chapter 8.8 “Error at gateway reset”
on page 45.
f
Reconnect gateway
(see chapter 4.7 “Connecting the
gateway” on page 18).
(3)
If the error persists, reset and re-ini-
tialize all smoke alarm devices and
the gateway (see chapter 5 “Reset”
on page 25).
(4)
If the previously mentioned measures
do not work, contact product
support (see chapter 11.2 “Product
support” on page 48).
8.7 Error in the radio connection
(smoke alarm device reachability)
4
Procedure (network scan, test signal,
firmware update, read maintenance
data) is concluded with an error
message.
4
A wrong response or no response
from specific smoke alarm devices
or radio groups.
Possible causes:
Temporary radio fault
•
Interference due to other
radio-based devices
Remedy:
f
Repeat network scan
(see chapter 4.9 “Network scan” on
page 21).