Switch-on delay
0 s … 24 h
Basic setting: 0 s
The load switches on after a
delay. Repeated switch-on
commands restart the delay
time. If the load has not yet
been switched on due to the
delay when a switch-off
command comes, then the
load will remain off.
In Flashing operating mode,
the pause times are set using
this parameter.
Note: The set time apply to
operation using radio
transmitters. The relay is
switched immediately when
the
Prog
button is pressed.
Switch-off delay
0 s … 24 h
Basic setting: 0 s
The load switches off after a
delay. Repeated switch-off
commands restart the delay
time. If the load has not yet
been switched off due to the
delay when a switch-on
command comes, then the
load will remain on.
In Flashing operating mode,
the pulse times are set using
this parameter.
Note: The set time apply to
operation using radio
transmitters. The relay is
switched immediately when
the
Prog
button is pressed.
Run-on time
0 s … 24 h
Basic setting: 0 s
As soon as a run-on time has
been entered, the actuator will
no longer remain on
permanently, but only for the
length of the run-on time. The
run-on time is restarted if
actuation is repeated. This
parameter is directly
connected to the "Manual
switch-off of run-on time"
parameter.
Note: The set time apply to
operation using radio
transmitters. The relay is
switched immediately when
the
Prog
button is pressed.
Behaviour after the end of the
disabling function
On
Off
no change
Last value
Basic setting: No change
Behaviour of the output when
a block is removed.
Behaviour on voltage return
On
Off
Last value
Configured brightness
Basic setting: Off
Defines the behaviour of the
output after voltage return.
RMD design: Bus voltage
return
8/11
82581713
J:0082581713
11.03.2014
eNet
Radio switch actuator for rail mounting, 1-channel