Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
i
To exclude any inadvertent activation of Programming mode during 'normal' use of the
control surface in later operation, the time between the first and the second actuation must
be at least 200 ms. Pressing simultaneously (time between first and second actuation
< 200 ms) will not result in an activation of Programming mode!
o
Program the physical address with the help of the ETS.
o
Programming mode ends:
- Automatically after adoption of the physical address
- By pressing a button on the TSM
i
If Programming mode is to be activated or deactivated in a device which is already
programmed with a valid application, there is the possibility that telegrams will be
transmitted to the bus at the time the button is pressed. The telegram transmitted depends
on the button function programmed.
i
The extension module does not receive any physical address of its own. It is activated by
the application program loaded in the TSM. The programming mode cannot be activated or
deactivated on the extension module.
When programming mode is active, the extension module can be operated normally. Then
the telegrams corresponding to the project design are also transmitted to the bus.
Programming the application program
Program the application into the device with the help of the ETS. Commissioning using ETS of
version 5 or higher is also possible.
The ETS detects automatically whether a valid application has already been programmed into
the device before. To reduce the programming time, the ETS downloads the whole application
only if the device was programmed beforehand with another application or with no application at
all. In all other cases, the ETS makes a time-optimised partial download in which only the
modified data is loaded into the device.
Installing the decorative control surfaces
The decorative control surfaces are available as a complete set of buttons. Individual buttons or
the complete set of buttons can be replaced using buttons with icons.
The design control surfaces are not included in the scope of supply of the device or the
extension module. These must be ordered specially according to the required design.
o
Place control surfaces on the device in the right orientation and also on the extension
module (if used), and snap in with a short push.
Page 20 of 309
Installation, electrical connection and operation