Assign physical address.
The programming LED goes out.

Label device on the side with physical address.

Load the application software into the device.

In case of active temperature measurement ("Universal" version) compare the temperat-
ure measurement.

Testing the detection field

In the case of presence detectors connected in parallel, check the detection fields individually
one after the other.

The presence detector is mounted and connected. The physical address and application soft-
ware are loaded.

Activate walking test:
Activate parameter "walking test after download" and download application software.
The presence detector operates independently of the brightness. All sensors are active
according to their programmed sensitivity.

Pace off the detection field, paying attention to reliable detection and interference
sources.
Any motions detected are displayed by the blue status LED in the sensor window.

Limit detection area, if necessary, using the push-on cover. Adjust sensitivity with blue
sensitivity switch (7) or IR remote control, or change the programming.

Deactivate parameter "walking test after download" and download application software.

Only for "Universal" version:

If enabled, the walking test function can be activated with the button 

Ù

 of the IR re-

mote control.

7

Disposal of batteries

Remove empty batteries immediately and dispose of in an environmentally friendly
manner. Do not throw batteries into household waste. Consult your local authorities
about environmentally friendly disposal. According to statutory provisions, the end

consumer is obligated to return used batteries.

8

Technical data

KNX medium

TP256

Commissioning mode

S-mode

Rated voltage KNX

DC 21 ... 32 V SELV

Current consumption KNX

max. 10 mA

Connection type for bus

device connection terminal

Protection class

III

Ambient temperature

-25 ... +55 °C

Storage/transport temperature

-25 ... +70 °C

Relative humidity

10 ... 100 % (no moisture condensation)

Degree of protection

IP44

Dimensions
Ceiling cut-out Ø×D

44 × 35 mm

Dimensions Ø×H

53.5 × 38 mm (with design ring)

Motion detection

11 / 13

82589823

25.02.2020

j0082589823

Summary of Contents for 3361-1MWW

Page 1: ...es can be swallowed This can lead directly to death by suffocation Danger ous substances may cause severe internal burns leading to death within 2 hours Keep new and used batteries away from children...

Page 2: ...it 3 PIR sensors Detection field 360 Integrated brightness sensor Deployed as presence detector motion detector or for alert operation Output functions Switching staircase function switching with forc...

Page 3: ...ety instructions Keep contacts of batteries and device free of grease Insert the supplied battery with correct polarity see IR remote control imprint Function buttons IR remote control Button Function...

Page 4: ...hanging settings with IR remote control If enabled individual settings for function block 1 can be changed during operation using a re mote control Sensitivity Increase sensitivity Press button Decrea...

Page 5: ...rection of motion of persons in the detection field Figure 4 The detection field becomes larger the greater the installation height while the detection density and sensitivity are reduced at the same...

Page 6: ...ce detector Installation height should not be more than 3 5 m otherwise fine detection is not possible The device has three independent sensors for motion detection The arrangement of the sensor areas...

Page 7: ...urement Figure 7 Installation height H R1 R2 2 20 m 1 5 m 2 3 m 2 50 m 1 8 m 2 6 m 3 00 m 2 0 m 3 0 m 3 50 m 2 5 m 3 6 m 4 00 m 2 8 m 4 2 m 5 00 m 3 5 m 5 2 m Light falling directly onto the sensor or...

Page 8: ...unting align the device so that the brightness sensor 10 is not facing the win dow Figure 7 Already pay attention to correct alignment when mounting the appliance box and support ing frame Connecting...

Page 9: ...ush friction springs 13 in the right orientation on the guides 2 from behind until they snap into place Figure 9 Connecting and fitting the device in a flush mounted box Figure 10 Flush mounted box 11...

Page 10: ...ied rubber grommet Cut the rubber grommet appropriately for the bus cable Route the bus line into the surface mounted housing Mount the surface mounted housing 15 on the room ceiling at the designated...

Page 11: ...rea if necessary using the push on cover Adjust sensitivity with blue sensitivity switch 7 or IR remote control or change the programming Deactivate parameter walking test after download and download...

Page 12: ...witches off briefly and then on again immediately Cause 1 Luminaires in the detection field Set the configuration barrier parameter so that cooling light bulbs are not detected Cause 2 The brightness...

Page 13: ...es not evaluate the first motion impulse detec ted Check programming Set and program device as motion detector Cause 2 Evaluation delay is activated so that anyone briefly entering the detection field...

Reviews: