Switch actuator / blinds actuator
–
Document all passwords and keep them safe.
Observe ambient temperature. Ensure adequate cooling.
■
Mount device on DIN rail.
■
In secure operation: The device certificate must be removed from the device and stored
securely.
Connecting the device
Figure 3: Device connection (connection example):
■
Connect the bus line with the KNX connecting terminal with the correct polarity.
■
Attach the cover cap to the KNX connection as protection against hazardous voltages.
■
For switched loads, configure the outputs as a switching output.
■
For Venetian blind operation, configure the outputs as a Venetian blind output. Two adja-
cent relay outputs form a Venetian blind output.
Delivery state: The outputs can be manually operated. Outputs are set as venetion blind
outputs.
The total current capacity of neighbouring outputs is a maximum of 20 A.
Figure 4: Total current capacity of neighbouring outputs
5.2 Commissioning
Load physical address and application program
■
In Venetian blind operation: measure blind/shutter and slat travel times and enter them in
the parameter setting.
■
Press the programming button.