Switch actuator / blinds actuator

Document all passwords and keep them safe.

Observe ambient temperature. Ensure adequate cooling.

Mount device on DIN rail.

In secure operation: The device certificate must be removed from the device and stored
securely.

Connecting the device

Figure 3: Device connection (connection example):

Connect the bus line with the KNX connecting terminal with the correct polarity.

Attach the cover cap to the KNX connection as protection against hazardous voltages.

For switched loads, configure the outputs as a switching output.

For Venetian blind operation, configure the outputs as a Venetian blind output. Two adja-
cent relay outputs form a Venetian blind output.

Delivery state: The outputs can be manually operated. Outputs are set as venetion blind
outputs.

The total current capacity of neighbouring outputs is a maximum of 20 A.

Figure 4: Total current capacity of neighbouring outputs

5.2 Commissioning

Load physical address and application program

In Venetian blind operation: measure blind/shutter and slat travel times and enter them in
the parameter setting.

Press the programming button.

6 / 9

82402603

15.05.2020

J0082402603

Summary of Contents for 230061SR

Page 1: ... Do not connect loads for mains voltage and SELV PELV together to the device For parallel connection of several motors to an output it is essential to observe the correspond ing instructions of the manufacturers and to use a cut off relay if necessary The motors may be destroyed Use only venetian blind motors with mechanical or electronic limit switches Check the limit switches for correct adjustm...

Page 2: ...otential free contacts Switching of electrically driven Venetian blinds roller shutters awnings and similar hangings Mounting on DIN rail according to EN 60715 in small distribution boards Product characteristics Outputs can be operated manually construction site mode Feedback in manual mode and in bus mode Disabling of individual outputs manually or by bus Status feedback e g wind alarm KNX Data ...

Page 3: ...h off adjust slats or stop Long Move hanging downwards 11 LED Dž ON relay outputs open manual control active 12 Button ALL OFF Open all relay outputs stop drives In operation with the button field the device distinguishes between a short and a long press Short actuation for less than 1 s Long actuation of between 1 and 5 s In switching operation the device distinguishes between the operating modes ...

Page 4: ...manual operation is switched off Switching outputs depending on the programming the output relays switch to the position that is active after the manual mode is switched off e g to the forced position logic func tion Blind shutter outputs depending on the programming the hangings move to the position that is active after the manual mode is switched off e g to the forced position safety or sun prot...

Page 5: ... Press button ǃ 6 repeatedly until LED A1 4 of the desired output or output pair flashes Press the DŽ 9 and Dž 10 buttons simultaneously for approx 5 s Selected output is disabled The status LED A1 4 of the selected output or output pair flashes quickly A disabled output can be operated in manual mode Re enabling outputs The device is in continuous manual mode One or more outputs were disabled in ma...

Page 6: ... voltages For switched loads configure the outputs as a switching output For Venetian blind operation configure the outputs as a Venetian blind output Two adja cent relay outputs form a Venetian blind output Delivery state The outputs can be manually operated Outputs are set as venetion blind outputs The total current capacity of neighbouring outputs is a maximum of 20 A Figure 4 Total current cap...

Page 7: ...ut ETS programming Master reset The master reset restores the basic device setting physical address 15 15 255 firmware re mains in place The device must then be recommissioned with the ETS Manual operation is possible During secure operation A master reset deactivates device security The device can then be re commissioned with the device certificate Performing a master reset Precondition The safe ...

Page 8: ...ormer 1200 VA Fluorescent lamps T5 T8 uncompensated 1000 W parallel compensated 1160 W 140 μF twin lamp circuit 2300 W 140 μF Compact fluorescent lamps uncompensated 1000 W parallel compensated 1160 W 140 μF Mercury vapour lamps uncompensated 1000 W parallel compensated 1160 W 140 μF Fitting width Art no 230061SR 72 mm 4 module Art no 230161SR 144 mm 8 module Art no 230241SR 216 mm 12 module Weigh...

Page 9: ...s provided in accordance with statutory requirements via the specialist trade ALBRECHT JUNG GMBH CO KG Volmestraße 1 58579 Schalksmühle GERMANY Telefon 49 2355 806 0 Telefax 49 2355 806 204 kundencenter jung de www jung de 9 9 82402603 15 05 2020 J0082402603 ...