4
4
English
Dimensions [mm]
A
B
C
D
E
...25/2 ME 520
330
250
140
180
...25/2 M
485
330
250
140
180
...35/2 M
520
330
250
140
180
...36/2 M
520
330
250
140
180
...45/2 M
520
330
255
140
180
...75/2 M
665
430
400
150
210
...76/2 M
665
430
400
150
210
Jung Pumpen GmbH • Industriestr. 4-6 • 33803
Steinhagen
XX1
DIN EN 12050-1
Wastewater lifting plants for buildings, DN 32
See "Technical Data" for pump performance
Noise emission value < 70 dB(A)
Corrosion protection – synthetic resin coating
1
The first two figures of the pump number indicate
the year of manufacture
Jung Pumpen GmbH • Industriestr. 4-6 • 33803
Steinhagen
XX
1
DIN EN 12050-2
Wastewater lifting plants for faecal-free wastewa
-
ter, DN 32
See "Technical Data" for pump performance
Noise emission value < 70 dB(A)
Corrosion protection – synthetic resin coating
1
The first two figures of the pump number indicate
the year of manufacture
Where no explosion protection is stipulated for
the pumping of foul wastewater at the instal
-
lation location, UAK pumps may also be used.
Electrical connection
By using our controls, you can be sure that the
requirements of the EU type-testing certificate
are met.
Only qualified electricians may carry
out electrical works to the pump or
the controls.
The standards applicable in each case (e.g. EN),
the country-specific regulations (e.g. VDE in
Germany), and the regulations of the local sup
-
ply network operator must be observed.
ATTENTION!
Never lay the end of cables in wa
-
ter! Penetrating water may cause malfunctions
.
Circuitry for pumps running on alternating cur
-
rent
The alternating current pumps must not be
used without a control unit.
MultiCut pumps in alternating current versions
are protected by 2 winding thermostats and a
motor contact switch in the AD 12 Ex ME con
-
trol unit. The two operating condensers in the
control unit must be dimensioned according to
the measurements indicated in the Type Exami
-
nation Certificate.
Capacity 2 x 30 µF Tolerance
±
10%
Operating voltage 400 V , Operating mode DB
Circuitry for low voltage (23291)
Circuitry for high voltage (23290)
Circuitry for high voltage, 75/2 and 76/2-pumps
(29713)
Alterations to the circuitry are to be made us
-
ing crimp connectors (X) between the coni
plug connection (Y) and the built-in motor. The
new crimp connection must be professionally
made.
Only slow-blow fuses or automatic fuses with C
or D characteristics are to be used as pre-fuses
for the pump. Necessary fuse protection for di
-
rect on-line start: 16 A, and for star-delta start
20 A (72/2, 76/2 M).
The pump must be protected via an overload
trip. Setting for direct on-line start = nominal
current, and for star-delta start = nominal cur
-
rent x 0.58.
If the protective device has been triggered, the
cause of the malfunction must be eliminated
before switching on again.
Potential equalisation
To comply with EN 60079-14 and EN 1127-1,
an additional equipotential bonding must be
installed for facilities with protective earth con
-
ductors in TN/TT networks in areas subject to
explosion hazards. In Germany, for example,
the design must be in accordance with VDE
0100, Part 540 (Association of German Electri
-
cal Engineers).
No additional potential equalisation is required
on site for JUNG PUMPEN concrete or plastic
chambers in explosion zones 1 and 2 (state
-
ment made by TÜV Nord (Technical Inspection
Agency) in March 2008).
Exception: if conductive parts, such as cable
protection sleeves made of corrugated pipe or