3 Electrical connection
34
V1.00/EN/00709718 [Thyristor power switch TYA S201]
Voltage supply
for
fan
3.3 Connection diagram
Control section
A
Depending on the mains voltage, the fan terminal X14 must be supplied with
the voltage specified below.
The lead protection must be between 2 A and a maximum of 5 A.
The fan is temperature-controlled, switches on automatically when the device
temperature reaches 85 °C, and remains in operation until the device tempera-
ture falls below 70 °C.
Mains voltage at the pow-
er controller
Tolerances
Fan specifica-
tions
Mains voltage AC230 V
-15 to +10 %, 48 to 63 Hz
AC 230 V/30 VA
Mains voltage AC400 V
Mains voltage AC460 V
Mains voltage AC500 V
Connection for
Screw terminals
Connection
Voltage supply for control electronics
(corresponds to the mains voltage of the
ordered device type)
L1
N/L2
V
Load connection in the
power section
and
protective conductor connection
U1
U2
PE
Fan X14
20, 21
(only for load current of
250 A)
L1
Mea
s
uring load voltage
Control-
electronic
Pha
s
e
(L1, L2, L3)
Pha
s
e
(L1, L2, L3)
oder N cond.
(N)
V
N/L2
TYA
U2
U1
Load
Pha
s
e
(L1, L2, L3)
PE
PE
TYA
20
21
Voltage
s
upply
for fan
Connection for
Screw terminal X2_1
Connection
Setpoint specification for current input
1
2
Setpoint specification for voltage input
(surge proof up to max. DC +32 V)
3 (GND)
(for permanent control)
4
Digital input PLC 0/24 V
ON logic level 1 = DC +5 to 32 V
OFF logic level 0 = DC 0 to < 5 V
3 (GND)
(for PLC logic signals)
4
Output DC 10 V fixed voltage
(max. +10 V, 2 mA)
5
Ground potential
6 (GND)
+
–
I
x
Current-
input
TYA
2
1
E
S
A
5
k
W
TYA
DC +10 V
4
3
+
–
U
x
3
5
4
external
S
etpoint
s
pecification with potentiometer
Voltage
input
Summary of Contents for TYA S201
Page 14: ...1 Introduction 14 V1 00 EN 00709718 Thyristor power switch TYA S201...
Page 21: ...V1 00 EN 00709718 Thyristor power switch TYA S201 21 2 Mounting TYA S201 250A...
Page 70: ...6 Special device functions 70 V1 00 EN 00709718 Thyristor power switch TYA S201...
Page 84: ...8 Error messages and alarms 84 V1 00 EN 00709718 Thyristor power switch TYA S201...
Page 86: ...86 V1 00 EN 00709718 Thyristor power switch TYA S201 9 What to do if...