![JUMO LOGOSCREEN 700 Brief Instructions Download Page 79](http://html1.mh-extra.com/html/jumo/logoscreen-700/logoscreen-700_brief-instructions_2031187079.webp)
79
6 Annex
6.1.4
Digital inputs/outputs
6.1.5
Relays
Number
Max. 24 (see connection diagram)
Input or output
Individually configurable as input or output
Input
Level
Logic level 0:
<
3.5 V; logic level 1:
>
10 V
Sampling rate
125 ms (max. counting frequency: 4 Hz)
Potential-free contact
R
ON
:
<
1 k
Ω
; R
OFF
:
>
50 k
Ω
(use of auxiliary voltage 24 V)
High-speed input
Usable inputs
1, 2 (see connection diagram)
Function
Counts each positive edge of the input signal
Max. counting frequency
12.5 kHz
Mark-to-space ratio
30 to 70 % (high-pulse
≥
30
μ
s, low-pulse
≥
30
μ
s)
Accuracy for
flow measurement
0.5 % of measured value; ambient temperature influence: 50 ppm/K
Output
Output signal
DC 0/24 V +10/-15 %; galvanically isolated
Current at option
- Analog(HI)/digital
Max. 40 mA per output, max. 50 mA in total per slot (including auxiliary voltage
supply current)
- Digital
Max. 40 mA per output, max. 100 mA in total (including auxiliary voltage supply
current)
Auxiliary voltage supply
Voltage
DC 24 V +10/-15 %
Current at option
- Analog(HI)/digital
Max. 50 mA per slot (including digital outputs current)
- Digital
Max. 100 mA (including digital outputs current)
Number
Max. 7 (see connection diagram)
Relay (changeover contact)
Switching capacity
3 A at AC 230 V or DC 30 V, resistive load
Contact life
30,000 switching operations at rated load