35
Parameter Explanation
Value range
factory-set Your
setting
SCL
start value of the
standard signal
-1999 to +9999digit
1
0
sCH
end value of the
standard signal
-1999 to +9999digit
1
100
SPL
lower
setpoint limiting
-1999 to +9999digit
1
-200
SPH
upper
setpoint limiting
-1999 to +9999digit
1
850
OFFS
process value correction -1999 to 9999digit
1
0
HySt
switching differential of
the limit comparator
0 — 9999digit
1
1
1.
For displays with one or two decimal places, the value range and the factory setting
change accordingly.
Example: 1 decimal place
→
value range: -199.9 to +999.9
q
C122
Timer signalling
X
0
no function
1
timer start until run-down
2
after run-down for 10sec
3
after run-down for 1min.
4
after run-down until
acknowledgement
q
C123
Unit of time (timer)
X
1
mm.ss (max. 99.59)
2
hh.mm (max. 99.59)
3
hhh.h (max. 999.9)
s = seconds; m = minutes;
h = hours
q
. . .
One output has to be configured
correspondingly(C113/C118).