8 Startup and parameterization
8.6.8
Configuring the transistor output DO1 to switch a load depending on two thresh-
old values
NOTE!
The units of the displayed values and the values to be entered manually correspond to the values se-
lected in chapter 8.6.2 "Choosing the flow rate unit, the number of decimals, and the counter display
unit", page 38.
OUTPUT
DO1
HYSTERES.
1- = 0.000
WINDOW
1. Enter a flow rate value
a
The flow
rate value corresponds to the low-
er threshold.
2. Confirm
a
In hysteresis mode: Value for 2- ≤ 2+ or 3- ≤ 3+.
In window mode: Value for 2- < 2+ or 3- < 3+.
1+ = 0.000
1. Enter a flow rate value
a
. The flow
rate value corresponds to the low-
er threshold.
2. Confirm
INV YES
INV NO
1. Choose the operating mode (in-
verted or not inverted) for the tran-
sistor output.
DO2
DEL. 1 = 00
In versions WITH relays
1. Enter the time delay before the
switching point (value between 0
and 99 s).
2. Confirm
RETURN
In versions WITHOUT relays