6 Technical data
16
6.4
Electrical data
Digital input DI1
Analog output AO1
Digital output DO1
Digital outputs DO2 and DO3
Voltage supply
DC 18 to 36 V, filtered and regulated
Tolerance of the applied voltage
±0,5 %
Current consumption
Max. 300 mA at DC 18 V
Switching voltage
DC 18 to 36 V
Safety
Protected against polarity reversal and voltage peaks, galvanically isolated
Input impedance
15 kΩ
Minimum pulse length
200 ms
Switching thresholds
PLC level: logical „0“ < 7 V, logical „1“ > 10 V
Type
Current output
Signal range
4 to 20 mA, sink or source (depending on the connection), 22 mA for reporting
faults
Load resistance
at DC 18 V
450 Ω
at DC 24 V
700 Ω
at DC 30 V
1000 Ω
at DC 36 V
1300 Ω
Type
Transistor output (open-collector output), NPN/PNP (depending on connec-
tion)
Function (adjustable)
Pulse output (default setting), hysteresis/window mode, reverse flow direction
message, generate a warning message
Pulse frequency
0 to 250 Hz
Switching voltage
DC 5 to 36 V
Switching current
Max. 100 mA
Duty cycle at f > 2 Hz
0,5
Minimum pulse length at f < 2 Hz
250 ms
Safety
Protected against excess voltage, polarity reversal, and short circuiting, gal-
vanically isolated
Type
Relay output
Function (adjustable)
Hysteresis (default setting), hysteresis/window mode, reverse flow direction
message, generate a warning message
Switching output
N/O contact
Switching capacity
3 A at AC 250 V resistive load, 3 A at DC 40 V resistive load
Operating life
100000 cycles
Galvanic isolation
Mixed switching of mains voltage AC 230 V and SELV or PELV voltage is
not admissible due to the basic insulation between the relays!