4 Mounting
4.3.8
Installation near pumps
4.3.9
Minimum clearance
4.3.10
Installation of the high-temperature version
•
We recommend using mechanical vibration
dampers for sensors that are installed near
pumps or other equipment generating vibra-
tions.
G00561
•
Maintain a minimum clearance of 0.7 m (2.3 ft)
between the devices to suppress any mutually
interference.
G01349
xx m (xx ft)
•
Complete thermal insulation of the sensor part
is required for the high-temperature version.
The pipeline and sensor insulation (1) must be
implemented as shown in the figure after in-
stalling the device.