3 Installation
14
3.9
Mounting
1. Mount the module on a 35-mm mounting rail according to EN 60715.
2. Install the module in a suitable housing in order to meet the requirements for the protection rating.
3.10
Connecting the lines
Screw connection
Admissible conductor cross section: 0.2 mm
2
to 2.5 mm
2
1. Strip 7 mm of the wire and provide it with ferrules.
2. Insert the wire into the relevant connection terminal.
3. Tighten the screw in the opening above the connection terminal using a screwdriver.
Connection torque: 0.6 Nm