JUMO ETH-20 Operating Manual Download Page 1

H

Please read these operating instructions before placing the
instrument in service. Keep the manual in a place which is accessible
to all users at all times. Please assist us in improving these operating
instructions where necessary. Your comments will be appreciated.
Tel49 661 6003-716
Fax

+49 661 6003-504

H

All necessary settings and manual changes within the device (if
required) are described in these operating instructions. If any
difficulties should nevertheless arise during startup, please do not
manipulate the unit in any way. By doing so, you could endanger
your rights under the instrument warranty! Please contact the
nearest subsidiary or the head office in such a case.

H

The instruments are maintenance-free. In the event of malfunction,
please return the instrument to the supplier with precise details of
the fault. The staff at our field offices, branches, and agencies are
always available to provide service and advice.

JUMO GmbH & Co. KG
Company address: Moritz-Juchheim-Strasse 1

36039 Fulda, Germany

Delivery address:

Mackenrodtstrasse 14
36039 Fulda, Germany

Postal address:

36035 Fulda, Germany

Phone:

+49 661 6003-716

Fax:

+49 661 6003-504

E-mail:

[email protected]

Internet:

www.jumo.net

JUMO Mess- und Regelgeräte Ges.m.b.H.
Pfarrgasse 48, 1232 Vienna, Austria
Phone:

+43 1 610610

Fax:

+43 1 6106140

E-mail:

[email protected]

Internet:

www.jumo.at

JUMO Mess- und Regeltechnik AG
Laubisrütistrasse 70, 8712 Stäfa, Switzerland
Phone:

+41 1 928 24 44

Fax:

+41 1 928 24 48

E-mail:

[email protected]

Internet:

www.jumo.ch

1. Introduction / Application

ETH series fitted thermostats are approved as:

safety temperature limiters (STB).

safety temperature monitors STW (STB)

Type examination to:

-  DIN EN 14597
- Pressure Equipment Directive 97/23/EC

Safety instructions

Physical and toxicological properties of substances which may escape,
should the system fracture:

H

Fitted thermostats of type series ETH comply with VDE 0631.

End of scale

Danger-

ous

reac-

tions

Fire/

explosion hazard

Water 

contami

nation

Toxicology

Ignition 

tempera-

ture

°C

Explosion 

limit

% v/v

irri-

tant

danger 

to health

toxic

liquid-filled

+200°C 

< +200 °C

no

+355 °C

0.6 - 8

yes

yes

1

no

+200 °C 

+350 °C

no

+490 °C

- -

yes

yes

1

no

gas-filled

+400 °C 

+500 °C

no

H

1

 

Should the measuring system fracture, the fill fluid may escape. At

present, there is no restrictive statement from the health authorities
concerning danger to health in the event of short-term exposure at low
concentration, for example, should the measuring system fracture.

2. Instrument identification / type 
declaration

Type designation

Nameplate

(reference example)
( 1 ) Type
( 2 ) Order code
( 3 ) Limit value/max. housing 

temperature/contact rating

( 4 ) Manufacturing number/

sales number

( 5 ) Mark of approval/

connection diagram

( 6 ) Year of manufacture
( 7 ) Week of manufacture

ETH . - . .

/

ETH

Fitted thermostat with microswitch
with capillary

-20

safety temperature monitor STW (STB),
with changeover contact

-70

Safety temperature limiter (STB)
with break contact and restart lockout

/au

gold-plated snap-action switch contact

/U

only with STB. microswitch with normally-closed 
contact, restart lockout, and
additional signal contact

B 60.2010.0

Operating Manual

2009-03-06/

00073781

3.

 

Mounting / general information

Capillary / temperature probe / pocket

General information

 If the capillary of the surface-mounting thermostat is cut through or becomes 

kinked, this could result in permanent device failure! 

 The minimum bending radius allowed for the capillary is 5 mm.

 JUMO pockets must be used when installing the temperature probe, if the approval 

for the surface-mounting thermostat is to remain valid.

 The temperature probe must be fully immersed in the measurement medium.

 When air is the measurement medium, you must choose a process connection 

without a pocket.

 To ensure the general accuracy of the operating value, the instruments must only 

be used with the pockets supplied on delivery (diameter D = 8, 10 mm).

 Only a probe of diameter d = 8 mm may be used in pockets of D = 10 mm.

 Multiple assignments of pockets are only allowed with 2 or 3 cylindrical probes of 

Ø 6 mm and pockets of 15 x 0.75 mm.

 If two probes are assigned, the spring clip provided on delivery must be installed in 

the pocket.

 With pockets U, US, E, ES, and EZS made from St 35.8I/16Mo 3 materials, the 

permitted operating period at operating temperatures above 420 °C is limited to 
200,000 hours. Compliance with TRD 508 is essential for applications in this range.

Mounting the thermostat head

Any installation position

Mount the thermostat head
On the chassis with 2 M3 screws

( 1 ) screw
( 2 ) panel

( 1 )

( 2 )

4.

 

Dimensions

Panel cut-out

Dimensions

ETHf-20

ETHf-70

Fitted thermostat

Type series ETH

ETH-20

ETH-70

Approved probes and pockets

A

U

UO

US

ES

Plain cylindrical probe

Screw-in pocket with screw-in 
spigot Form A to DIN 3852/2. 
With fixing screw

Pocket as screw-in pocket, with 
screw-in spigot Form "A" to 
DIN 3852/2, with fixing screw

Weld-in pocket
with fixing screw and clamp

For code "f" pocket as weld-in pocket, with 
welding shoulder; pocket secured with union nut, 
connection "C".

E

B

C

D

Q

V

( A ) = washer / ( B ) = seal

For code "f" pocket as screw-in 
pocket, with screw-in spigot 
Form A to DIN 3852/2; pocket 
secured with union nut, probe 
mounting "C"

Probe mounting "C"
with loose coupling, threaded at 
both ends

Plain cylindrical probe with 
shoulder and union nut. Shoulder 
brazed or welded to capillary

Plain cylindrical probe, threaded 
connector brazed or welded to 
capillary

For code "f" double threaded 
coupling for subsequent capillary 
mounting. Probe temperature 
max. +200 °C

For code "f" clamping gland for 
subsequent capillary mounting. 
Probe temperature max. +200 °C

SW

ØD

G

L1

S