6 Operation
38
Deactivate Manual mode
No simulation = No Manual mode, control is via device.
When the instrument is in display mode, the word MANUAL disappears from
the status line of the display.
6.8.3
Simulation of analog outputs via MANUAL mode
Release and activation
✱
Select activation of simulation of the actual value output:
ADMINISTR.-LEVEL/PARAMETER LEVEL/ANALOG OUTPUTS/ANALOG
OUTPUT 1 (2, 3)/SIMULATION/ON.
With "On" the output takes on the value of the "Simulation value" parameter.
When the instrument is in display mode, the word MANUAL appears in the
status line of the display.
Deactivation
✱
ADMINISTR.-LEVEL/PARAMETER LEVEL/ANALOG OUTPUTS/ANALOG
OUTPUT 1 (2, 3)/SIMULATION/OFF.
The corresponding output of the instrument works again.
When the instrument is in display mode, the word MANUAL disappears from
the status line of the display.
6.9
HOLD mode
In HOLD status the outputs take on the states programmed in the relevant
parameter (controller channel, switching output or analog output).
This function can be used to "freeze" switching outputs and the analog
outputs of the instrument. This means the current status of the output will be
retained even when the measured value changes. Control is not via the
instrument.
HOLD mode can be activated by pressing the key or by the binary input.
Activation by pressing key
✱
Press and hold the
and
keys longer than 3 seconds.
Then the outputs of the instrument respond according to the default
settings.
The word HOLD appears in the status line of the display.
If MANUAL mode is activated while HOLD mode is activated, MANUAL mode
takes precedence and MANUAL then appears in the status line of the display!
MANUAL mode can be terminated by pressing the
key.
If HOLD mode is still activated (by the binary input or by keyboard), the
instrument then returns to HOLD mode!
EXIT
EXIT
Summary of Contents for dTRANS CR 02
Page 83: ...83 12 Setup program Export data for processing in an external program...
Page 118: ...17 Index 118...