73
13 Configuration
13.3.3
Temperature input
13.4
IO-Link interface
13.4.1
SIO mode (switching outputs)
13.5
Sensor monitoring
NOTE!
Sensor monitoring requires plant-specific empirical values for the sensor stress caused by process con-
ditions. Configure the sensor monitoring parameters on the basis of these empirical values.
Sensor monitoring
Configuration item
Selection/setting op-
tion
Explanation
Temperature input
function
active
inactive
only for hardwired device versions:
Activation of the temperature input
Filter Time Constant
0.0 to 25.0 s
Optimization of measured value updating
The larger the value of the filter time constant, the slower is the
change in measured value at the output.
Offset
-10 to+10 °C
Correction value added to measured value
Connection type
2-wire
3-wire
only for device versions with a separate sensor
Connection variants for the connected resistance thermometer
Configuration item
Selection/setting op-
tion
Explanation
output signal
Limit value 1
Limit value 2
Sensor fault
Calibration timer
Calibration active
Digital signal source for the output
Inversion
Yes
No
Switching status inverted or not inverted
Output mode
p-switching
n-switching
Push/Pull
Output driver mode in the SIO mode
In the SIO mode, the IO-Link output allows the circuit variants
PNP (p-switching), NPN (n-switching) and Push/Pull. The out-
put driver must be set to the desired mode using this configura-
tion item.
Switching operations
limit value
0 to 99999 ×1000
The switching operations of the binary outputs are counted in
the device. When the limit value is reached, a service message
is shown
on device versions with a display
.
Setting 0 = Limit value monitoring inactive
Limit value ON period
0 to 99999 h
The total ON period of the binary outputs is counted in the de-
vice. When the limit value is reached, a service message is
shown
on device versions with a display
.
Setting 0 = Limit value monitoring inactive
Summary of Contents for digiLine CR HT10
Page 2: ......
Page 6: ...Contents...
Page 16: ...3 Device Description 16...
Page 26: ...4 Identifying the device version 26...
Page 50: ...10 Troubleshooting in the event of faults 50...
Page 70: ...12 IO Link data 70...
Page 78: ...14 Operation maintenance and care 78...
Page 83: ......