8 Technical Data
38
8.8
Electrical safety
8.9
Environmental influences
Clearances and creep paths
voltage supply AC 110...240V
voltage supply AC/DC 24V
Mains to electronic components and probe
≥
6 mm
/ ≥
8 mm
≥
6 mm
/ ≥
8 mm
Mains to the relay
≥
8 mm
/ ≥
8 mm
≥
8 mm
/ ≥
8 mm
Relay to electronic components and probe
≥
8 mm
/ ≥
8 mm
≥
6 mm
/ ≥
6 mm
Relay to Relay
≥
8 mm
/ ≥
8 mm
≥
8 mm
/ ≥
8 mm
Electrical safety
according to DIN EN 14597 (DIN EN 60730-1)
Overvoltage category III, pollution degree 2
Protection type I
with internal separation to SELV current circuits
Ambient temperature range
0 ... +55°C
Storage temperature range
-30 ... +70°C
Temperature coefficient
≤
±
0.005% / K dev. from 23°C
1
for RTD temperature probes
≤
± 0.01% / K dev. from 23°C
1
for thermocouples, current, voltage
Ambient conditions
85% rel. humidity without condensation
(3K3 with extended temperature range as per DIN EN 60721-3-3)
EMC
as per DIN EN 14597 and standards from the standard series DIN EN 61326
Interference emission
Class B
Interference immunity
Test level for protective, regulation and control devices (RS) as per DIN EN 14597
1All specifications referring to the measuring range limit value
Summary of Contents for B70.1170.0
Page 2: ...Bedien bersicht C111 oErr siehe Kapitel 7 Konfigurationsebene...
Page 35: ...7 Konfigurationsebene 33 2011 03 13...
Page 46: ...11 Zertifikat 2011 03 13 44 11 Zertifikat...
Page 56: ...15 Was ist wenn 2011 03 13 54...
Page 57: ...15 Was ist wenn 55 2011 03 13...
Page 58: ...15 Was ist wenn 2011 03 13 56...
Page 94: ...7 Configuration level 33 2011 03 13...
Page 105: ...11 Certificate 2011 03 13 44 11 Certificate...
Page 115: ...15 What to do if 2011 03 13 54...
Page 116: ...15 What to do if 55 2011 03 13...
Page 117: ...15 What to do if 2011 03 13 56...