9 Configuration – in setup program only
228
9.11.1
Formula
Customer-specific linearization is specified using a 4th order polynomial. The polynomial is calculated
for the entire linearization range.
Polynomial formula: y = X4*x
4
+ X3*x
3
+ X2*x
2
+ X1*x + X0
Setup dialog box
Parameter
The value range for the linearization (linearized values, y axis) is monitored in the module and limited as
follows:
Lower limit of the value range = Ymin - 0.0125 × (Ymax - Ymin)
Upper limit of the value range = Ymax + 0.03125 × (Ymax - Ymin)
NOTE!
A linearized value that lies outside of the value range results in a deviation above or below the measuring
range (out of range).
Parameter
Selection/settings
Description
Measuring range
start (Ymin)
-99999 ...
0
... +99999
Start value of the y axis
Always give a temperature value in °C.
Measuring range
end (Ymax)
-99999 ...
100
... +99999
End value of the y axis
Always give a temperature value in °C.
X0
-99999 ...
0
... +99999
Absolute component of the polynomial
(point of intersection with the y axis)
X1
-99999 ...
1
... +99999
Coefficient of the linear component (x)
X2
-99999 ...
0
... +99999
Coefficient of the quadratic
component (x
2
)
X3
-99999 ...
0
... +99999
Coefficient of the cubic component (x
3
)
X4
-99999 ...
0
... +99999
Coefficient of the quartic component (x
4
)