4 Ex relevant data for operation in zones 1, 21 and 22
4.2
Electrical data for operation in zones 1, 21, 22
4.2.1
Devices with HART protocol
When operating in potentially explosive areas, observe the following electrical data for the transmitter
signal inputs and outputs. For the current output version (active/passive), see the identification marking
in the device's terminal box.
Model: 406012/1-1, 406013/1-1, 406015/1-1, 406016/1-1, 406018/2-1 (dual-compartment housing),
406019/2-1 (dual-compartment housing)
All inputs and outputs are galvanically isolated from each other and from the voltage supply.
Operating
data
Ex-data – ignition protection type Ex i, IS
Inputs and U
N
I
N
U
O
U
I
I
O
I
I
a
a
Intrinsically safe single-channel or multichannel barriers (supply isolators) with resistance characteris-
tic curve must be used.
P
O
P
I
a
C
O
C
I
C
OPA
C
IPA
L
O
L
I
Outputs
[V]
[mA]
[V] [V] [mA] [mA] [mW] [mW] [nF] [nF] [nF]
[nF] [mH] [mH]
Current
output
Active
30
30
20 60 100
425
500
2000 210 8.4 195
24
6
0.065
Terminal
31/32
Current
output
passive
30
30
60
500
2000
8.4
24
170
Terminal
31/32
Digital
425
b
500
c
b
For "active" current output.
c
For "passive" current output.
output
DO2 pas-
sive
30
220
60
2000
3.6
3.6
170
Terminal
41/42
Digital
425
b
500
c
output
DO1 pas-
sive
30
220
60
2000
3.6
3.6
170
Terminal
51/52
Digital
input
DI
d
passive
d
Only available in conjunction with passive current output.
30
10
60
500
2000
3.6
3.6
170
Terminal
81/82