12
JUDO i-soft
Installation
–
Tightly fasten the four cylinder screws
M6x25.
The hand-wheel of the bypass valve can be
positioned anywhere above the unit or to the
side. Depending on conditions on site,
installation should be carried out ensuring
sufficient access to the hand-wheel.
4.4
Mounting the softener to the
pre-assembled bypass valve
The connection flange of the softener is
covered by a white protector cap. This pro-
tector cap is secured by two cylinder screws
M6x130 and two threaded bolts M6x137
with nuts.
Prior to removing the protector cap, the two
threaded bolts M6x137 with nuts have to be
removed and replaced with the provided
cylinder screws M6x130.
ATTENTION
Do not grasp into the connection flange
of the device after removing the white
protector cap (danger of high level pres-
sure)!
–
Loosen all four cylinder screws M6x130,
but don’t remove them (bayonet fixture)!
–
Remove the white protector cap.
The section of the profiled flange gasket
must point towards the bypass valve. Failure
to observe this can lead to leaks and water
escaping. This can in turn cause water
damage to the house and its installations.
–
Lift up the softener and swivel it through
approx. 30° in an anti-clockwise direction.
–
Position the softener on the flange of the
bypass valve marked with the cast in
letter “G” (unit flange) so that the screw
heads pass through the bayonet fixing
drill holes.
–
Swivel the softener through approx. 30°
back in a clockwise direction.
–
Tightly fasten the four cylinder screws
M6x130.
After assembling the softener unscrew the
wall support so far that it rests against the
softener casing and the softener hangs
vertically to the wall.
Select the torque (approx. 4 Nm) so
that the gasket closes!
Fig. 8:
Bypass valve
pipe flange ("R")
unit flange ("G")
built-in rotary flange
hand-wheel
Select the torque (approx. 4 Nm) so
that the gasket closes and the
softener is not damaged or strained!