background image

Installation and operating instructions

JUDO PROMI-PLUS

Domestic water station ¾" - 1¼"

Valid for: EU countries and Switzerland

Language: English

Read before use and store!

Summary of Contents for 8170200

Page 1: ...Installation and operating instructions JUDO PROMI PLUS Domestic water station 1 Valid for EU countries and Switzerland Language English Read before use and store...

Page 2: ...rinting even in excerpt form is only permitted with special approval Dear customers Thank you for the confidence you have shown in us by purchasing this prod uct You have purchased a state of the art...

Page 3: ...tallation of the device 9 3 4 Draining of the backwash water 10 3 5 Commissioning 11 4 Operation 11 4 1 Setting the downstream pres sure 11 4 2 Cleaning of the sieve insert backwashing 11 4 3 Conversi...

Page 4: ...omply with the European Drinking Water Directive 98 83 EC Before using the device with water that does not comply with this Direc tive it is essential to consult the manufac turer 1 2 2 Water pressure...

Page 5: ...rotary flange fitting must be fitted so that it is free from mechanical stress or strain Otherwise mechanical damage to the pipe or the rotary flange fitting up to and including breaks can result For...

Page 6: ...to the device e g Direction of flow arrow Type label Cleaning information must be observed and maintained in legible condition 1 5 Units used Unit Conversion bar 1 bar 105 Pa 0 1 N mm2 DN 20 1 DN 25...

Page 7: ...f the pressure reducer 10 Inlet pressure gauge 11 Outlet pressure gauge 12 Outlet backwash water 2 3 Materials used The materials used are resistant to the physical chemical and corrosive loads expect...

Page 8: ...test according to DIN EN 13443 1 and DIN 19628 and are therefore not permitted to wear the approval mark 3 Installation CAUTION The device may only be installed by qualified technical personnel Insta...

Page 9: ...ce CAUTION If no bypass valve is installed a shut off valve must be installed upstream and downstream of the unit in order to interrupt the water supply during installation mainte nance repair or malf...

Page 10: ...of the wastewater can be drained simulta neously If a wastewater connection directly beneath the device is not possible the backwash water can be drained away via a hose or a pipe that is connected fr...

Page 11: ...ia the pressure reducer The factory pre set downstream pressure of 4 bar can be changed to a value between 1 5 bar and 6 bar depending on the upstream pressure 1 Undo the countersunk screw on the hand...

Page 12: ...a more frequent backwashing is necessary 4 2 2 Due date of backwashing Every two months a beep reminds you that the backwashing is due To switch off the beep press the reset but ton on the handwheel c...

Page 13: ...ts WARNING The device may only be repaired by qualified technical personnel Only use original spare parts for repairs Before performing work on the device that goes beyond pure operational use the dev...

Page 14: ...the flange surfaces against damage to ensure proper sealing Protect the device from dirt so as not to impair drinking water hygiene Store the device in a frost free place to prevent damage caused by...

Page 15: ...line cracks on the filter bowl Filter bowl was exposed to high temperatures or solvents Inform the installer or the closest customer ser vice point If water escapes close shut off valves Have the filt...

Page 16: ...ecked annually on the outlet pressure gauge both at zero flow and at peak flow large withdrawal If necessary the setting of the outlet pressure must be readjusted To ensure the process operates succes...

Page 17: ...bar 1 5 bar 6 bar Factory setting of downstream pressure 4 bar 4 bar 4 bar Mesh size sieve insert2 100 m 0 1 mm 100 m 0 1 mm 100 m 0 1 mm Water temperature and ambient temperature max 30 C max 30 C m...

Page 18: ...th of the device C Height above the pipe middle D Height below the pipe middle E Installation depth up to the pipe middle F Waste water connection up to the pipe middle G Waste water nominal diameter...

Page 19: ...Technical data 7 3 Spare parts 1702272 2020 07 JUDO JPM 19...

Page 20: ...r alarm consisting of pos 1 2 3 1 2010495 49 1 Handwheel lid 1 2 Backwash reminder alarm 1 3 Battery 1 5 V Typ AAA set with 2 pcs 1 2060347 8 4 Countersunk screw M5 12 1 5 Disc A 6 4 1 6 Memo handwhee...

Page 21: ...sieve 1 33 O ring 25 3 5 1 34 O ring 52 3 5 1 35 Cylinder screw M6 25 Set with 4 pcs 1 2060333 2 36 Pressure gauge seal 2 37 O ring 14 5 2 5 4 38 Pressure gauge connection piece 2 39 Pressure gauge 0...

Page 22: ...recycling system To protect environment old appliances and used batteries must not be disposed of with household waste Instead use the local col lection and return points which are commit ted to free...

Page 23: ...Maintenance log 9 Maintenance log Product designation Domestic water station Order number Serial number Date Work activities performed Company signa ture 1702272 2020 07 JUDO JPM 23...

Page 24: ...judo online ch judo online ch BENELUX JUDO Wasseraufbereitung GmbH Filiaal Filiale Benelux Laarbeeklaan Av du Laerbeek 72 A1 B 1090 Brussel Bruxelles Phone 32 0 24 60 12 88 Fax 32 0 24 61 18 85 E mai...