Specifications
Operating instructions
16
6
Specifications
Designation
Values
Anolyte neutral production rate
30 L / h
Anolyte production rate
20 L / h
Catholyte production rate
20 L / h
Free chlorine (in NaClO in accordance with EN 901)
<200 mg / L
Disinfectant Anolyte or Anolyte neutral
Selectable
Disinfection of hot and cold water
5 – 65 °C)
Connection dimension of Anolyte storage tank
DN 8
Drinking water inlet pressure
3 - 10 bar
System pressure
1.8 bar
Process adjuvant - high-purity saturated saline
solution
0.5 - 2 g / L Anolyte / Anolyte
neutral
System control, automatic process control
5 control elements, PLC
Anolyte dosing pumps can be connected
Max. 2
Disinfectant solution / Calzid-Ex level monitoring
Inductive switch
Process unit cleaning with Calzid-Ex
Automated
Calzid-Ex consumption
Depending on drinking water
hardness
Ambient operating temperature
15 – 35 °C
Relative humidity
< 45 %
Protection class
IP54
Power supply
230 V AC ± 10%, 50 Hz
Power consumption
350 W
Fuse
13 A
Drinking water connection
DN 15, AG ½“
System inlet
50 L / h drinking water quality
Water hardness system inlet
< 2°dH
Temperature at system inlet
15 – 22 °C
Water pressure at system inlet
min. 3 bar
Waste connection
min. DN 65
Exhaust air connection (pipe with diffusion barrier)
min. DN 20
Room ventilation
min. 20 m³ / h