10.9 Digital Output Group
Pr.012
DO Status
This parameter shows the DO1 ~ DO16 status by hexadecimal numerical data. Converting this
data to be binary format, status of DI1 ~ DI16 will be presented from LSB to MSB of the data.
For example:
if Pr.012=0
Converting to binary is “0000 0000 0000 0000”. The DO1 ~ DO16 are OFF.
If Pr.012=5
Converting to binary is “0000 0000 0000 0101”. The DO1 and DO3 are ON, and
others are OFF.
Pr.013
DO Simulation
This parameter can be set to a decimal value, and start the drive that DO startup / shutdown
。
If = 0
Converting to binary is 0000 0000 0000 0000;
Expanded bit by the binary state, you can perform communication: All of the DO
terminal status = OFF
。
If = 5
Converting to binary is 0000 0000 0000 0101
Expanded by the binary bit status, communication execution: DO1 and DO3 state is ON,
the remaining terminals are OFF
。
Pr.111
DO-1 function Select
Pr.112
DO-2 function Select
Pr.113
DO-3 function Select
Pr.114
DO-4 function Select
This parameter group to set the digital output terminal options
。
【Note】
The four belonging 24V-OpenCollector generally optically coupled isolated digital input,
scan execution time is 400us
。
Related options, refer to Chapter 12: Digital output terminal function selection
。
Pr.165
DO-15 function Select (Firmeare Modify)
Pr.166
DO-16 function Select (Firmeare Modify)
This parameter group to set the digital output terminal options
。
【Note】
The two belong internal firmware analog digital output, scan execution time is 400us
。
Related options, refer to Chapter 12: Digital output terminal function selection
。
DI-15 and DO-15 internally connected together
DI-16 and DO-16 are connected together internally