History screen
Figure 36: History screen
This screen allows the user to browse through the faults. For a more thorough reporting of the
system conditions at the time of the recorded shutdown, use the
.
Table 67: Display only fields
Field/LED name
Description
Last Normal Shutdown
Displays the date and time and the description of the last normal shutdown. A normal
shutdown is defined as:
•
Local (Panel rocker switch)
•
Remote (Digital, Analog, or BAS (ISN))
Last Fault While Running
Displays the date and time and the description of the last safety or cycling shutdown while
the system was running.
Last Ten Faults
Displays a chronological listing (most recent first) of the date, time, and description of the
last 10 safety or cycling shutdowns that occur while the system is running or stopped.
Table 68: Programmable
Button
Description
Print History
Generates a report listing the status of the parameters at the time of the selected shutdown.
Print All Histories
Generates a report listing the status of the parameters at the time of each stored shutdown.
Table 69: Navigation
Button
Description
Home
Returns to the Home screen.
View Details
Causes a move to a subscreen containing the value of select chiller parameters at the time of
the associated shutdown.
Trending
Causes a move to a subscreen allowing the user to view trending data on selected chiller
parameters.
Custom View
Causes a move to a subscreen allowing the user to view the Custom Setup Screen.
Page Up
Allows the user to scroll up to the first history fault.
Page Down
Allows the user to scroll down to the last history fault.
73
YVAM Control Center
Summary of Contents for YORK YVAM 0350
Page 2: ...2 YVAM Control Center...
Page 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Page 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Page 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Page 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Page 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Page 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Page 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Page 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Page 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...