Johnson Controls York YIA Series Wiring Diagram Download Page 7

7

JOHNSON CONTROLS

FORM 155.21-W2 (1209)

LD06828

FIG. 10 – 

MULTI-UNIT SEQUENCE

MULTI‑UNIT SEQUENCE

For multiple chiller installation application, Multi-Unit 

Sequence contacts are available to start and stop each 

unit. The main tained closure of a device contacts across 

terminals   

1

   and    

9

    will permit the unit to operate 

in all the operating modes with the “

UNIT

” switch in 

the “

RUN

” (

l

) position. Conversely, an opening of the 

device con tacts will inhibit the unit from operating; the 

OptiView™ Control Center will then display the fol‑

lowing message: “CYCLING SHUTDOWN – AUTO 

RESTART”  and  “UNIT  SHUTDOWN  BY  MULTI-

UNIT REMOTE

”.

 CONDENSER FLOW SENSORS

The Thermal-type analog flow sensor interfaces with 

the  Microboard  and  Paddle-type  digital  flow  sensor 

interfaces with the I/O board.

For the program to read the appropriate inputs for the 

flow sensor status, the actual flow sensor type used must 

be  entered  at  the  keypad  SALES  ORDER/CONFIG 

Screen using Service Access Level.  Enter "ANALOG" 

for Thermal-type or "DIGITAL" for paddle type.  

When flow is sensed, the flow sensor contacts are closed.  

Opening of the flow sensor contacts (no flow) for 30 

continuous seconds causes a safety shutdown displaying 

"CONDENSER - WATER FLOW SWITCH OPENED".  

The flow sensor status is bypassed for the first 30 seconds 

of "SYSTEM RUN".

THERMAL TYPE FLOW SENSOR

When the Thermal-type flow switch is used, the flow 

switch uses the cooling effect of liquid to sense flow.  

When the flow of liquid is sensed, the solid state relay 

output is turned on conducting current through the mi‑

croboard load resistor to the +5VDC applying greater 

than +4VDC to the microboard input J14-8.  

When no flow of liquid is sensed, the solid state relay 

output  is  turned  off,  this  results  in  less  than  1VDC 

to  the  microboard  input  and  the  OptiView  Control 

Center will display the following message: “SAFETY 

SHUTDOWN ” and “CONDENSER WATER FLOW 

SWITCH OPEN”.

FIG. 11B – 

PADDLE TYPE FLOW SENSOR

LD06827

PADDLE TYPE FLOW SENSOR

If desired, a condenser water flow interlock can be ap

plied. Flow switch – McDonnel type FS8W, max. 150 

psi (YORK Part No. 024-26116) available at additional 

cost. If condenser water flow switch is not used, a jumper 

must be installed between terminals  1  and 11 .
When condenser water is flowing, the flow switch con

tact will close. Opening of the condenser water flow 

switch contacts for 30 continuous seconds will cause 

unit shutdown. The Flow Switch Status is checked 30 

seconds into “System Run” and continuously thereafter. 

The OptiView Control Center will display the following 

message: “SAFETY SHUTDOWN” and “CONDENS

ER WATER FLOW SWITCH OPEN”.

LD14443

I/O BOARD

PADDLE-TYPE FLOW SENSOR

(DIGITAL)

CONTACTS RATED 

5mA @ 115VAC

or

CONDENSER WATER

PUMP INTERLOCK

MICROBOARD

THERMAL-TYPE FLOW SENSOR

(ANALOG)

FIG. 11 ‑

 CONDENSER FLOW SENSORS

The OptiView Control Panel allows the use of either the 

Thermal-type or Paddle-type flow sensor.

Summary of Contents for York YIA Series

Page 1: ...nnection for the following operations Remote Stop Contacts See Fig 8 Remote Start Contacts See Fig 8 Remote Local Cycling Devices See Fig 9 Multi unit sequence See Fig 10 1 The OptiView Control Center...

Page 2: ...ndividual shall also be familiar with and comply with all applicable governmental standards and regula tions pertaining to the task in question safety symbols The following symbols are used in this do...

Page 3: ...L OPERATION INDIVIDUAL UNIT PUMPS 9 FIG 15 MULTIPLE UNITS TWO PARALLEL OpERATION SINGLE CHILLED WATER PUMP 9 FIG 16 REMOTE Steam Hot Water Limit SETPOINT with 0 10vdc signal 10 FIG 17 REMOTE Steam Hot...

Page 4: ...R14 2 R58 R52 R50 R40 R38 R22 C8 R16 CR5 R56 R60 R54 R44 R42 R34 R36 R32 R26 R28 R24 R20 R18 R17 R1 R13 U1 U4 U3 R3 R15 R11 U5 R5 C1 CR2 CR3 CR8 RV7 CR7 RV6 CR6 RV3 RV2 R30 R2 Q2 R10 R4 U2 R12 R6 U6...

Page 5: ...View Control Center is in digital analog or ISN remote op erating mode allow ing for energy management system or remote start stop control Fig 8 2 All chiller safety cut out controls are in the normal...

Page 6: ...D06824 N O CONTACTS IN CONTROL CENTER RATED 2 AMPS INDUC TION AT 250VAC 30VDC 5 AMPS RESISTIVE AT 250VAC 30VDC closure of the Energy Management System Remote Stop Contacts causes the chiller to shutdo...

Page 7: ...l type flow switch is used the flow switch uses the cooling effect of liquid to sense flow When the flow of liquid is sensed the solid state relay output is turned on conducting current through the mi...

Page 8: ...tat RWTwill automatically cycle either 1 or 2 unit Timer 3TR is an additional feature which prevents simultaneous starting of lead and lag unit following a power failure and eliminates nuisance starti...

Page 9: ...p is avoided When one unit is cut out by the sequence control Fig 12 the temperature of the supply chilled water does not change MULTIPLE UNITS TWO PARALLEL OpERATION SINGLE CHILLED WATER PUMP For thi...

Page 10: ...inputs as follows Example if the input is 3VDC the setpoint would be set to 73 as follows SETPOINT 100 3 x 9 100 27 73 Therefore a 2 second pulse 10 3 sec 20 4 sec 30 up to 11 sec which will 100 Calc...

Page 11: ...rammed a setpoint for 44 F base into the OptiView control center and the Remote Reset Range is programmed to be 10 F then the energy management system can remotely reset the setpoint over the range of...

Page 12: ...et Range setpoint is for 10 F and the local Leaving Chilled Liquid Temperature Setpoint is programmed for 40 F the setpoint would be set to 44 F as follows OFFSET F 5 1 10 10 4 10 10 40 10 4 F SETPOIN...

Page 13: ...following message SAFETYSHUTDOWN MANUALRESTART and the cause of shutdown RUN CONTACTS REMOTE RUN LIGHT AND SHUTDOWN INDICATOR PLUS EMS When run contacts are required for a Remote Run Light and or Shu...

Page 14: ...is flowing the flow switch con tact will close If the flow switch opens for 2 seconds the unit shuts down GENERATOR BACKUP TRANSFER During a prolonged power failure the unit will shutdown without goin...

Page 15: ...and TB6 in YORK OptiView Control Center as 115VAC source is fed from terminals 1 and 2 16 Entering and Leaving Chilled and CondenserWaterTem perature Sensors are supplied by YORK as a standard item on...

Page 16: ...861 1001 www york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by Johnson Controls Inc 2009 ALL RIGHTS RESERVED Form 155 21 W2 1209 NEW...

Reviews: