background image

13

JOHNSON CONTROLS

FORM 155.21-W2 (1209)

LD06836

FIG. 21 –

  RUN CONTACTS / REMOTE RUN LIGHT 

AND SHUTDOWN INDICATOR PLUS EMS

 12.  While the chilled water flow switch is tripped after 

shutdown as described in item (8) and the solution 

temperature is below 136°F, check for crystalliza

tion.

 13.  While the condenser water flow is tripped/open; if 

the solution temperature falls to less than 136°F, 

check for crystallization.

When all safety controls are satisfied, and the OptiV

iew control center "unit" switch has been placed in the 

"STOP/RESET" position, (de-energizing the alarm) and 

then in the "RUN" position, the unit may be restarted, 

if the control center is in "REMOTE" mode, via the 

Remote Start Contacts (FIG. 8); or if the control center 

is in "local" mode the unit may be started by pressing 

the  keypad-mounted  "unit"  switch  to  the  "START" 

position.

If the unit was shut down because of 

Cycling Shutdown Contacts (see FIG. 

4) the alarm will not be energized, but 

the unit will have been shut  down. A 

closure of the safety alarm contacts 

means that an operator must manually 

reset and restart the unit.

When the Safety Shutdown contacts close, the OptiV

iew™ Control Center will display the following message: 

“SAFETY SHUTDOWN – MANUAL RESTART”, and 

the cause of shutdown.

RUN CONTACTS/REMOTE RUN LIGHT AND 
SHUTDOWN INDICATOR PLUS EMS

When run contacts are required for a Remote Run Light 

and/or Shut down Indicator AND Energy Management 

System (EMS), connect (by others) as shown in the dia

gram. The EMS, control relay, shutdown and run lights 

are furnished by others. When the N.O. contacts close, 

between terminals 

35

  and 

36

  on field wiring terminal 

block TB2 in the OptiView Control Center, this indicates 

that the unit is operating; the Remote Run Light will be 

energized. The unit run contacts open when the unit is 

shutdown (safety or cycling) and the remote indica tor 

will then be energized. For run contacts to EMS only 

refer to Fig

. 6. When terminals  

35

  and  

36

  are not used 

for an EMS, they may be connected to a remote Run 

Light. The control relay scheme shown in 

Fig

. 21 can 

also be applied for a Remote Run Light and a Remote 

Shutdown indicator, when an EMS is not used.

LD06838

FIG. 22 –

 AUXILIARY SAFETY SHUTDOWN INPUT

The closure of a momentary or maintained N.O. Switch 

or Relay Contacts will cause the unit to shut down and 

display: system status - "RESET TO RESTART" and 

under fault message - "AUXILLIARY SAFETY SHUT

DOWN". The unit will not restart until the contacts open 

and the keypad "unit" switch is moved to the “STOP/

RESET” position and then to the “START”  position.

Summary of Contents for York YIA Series

Page 1: ...nnection for the following operations Remote Stop Contacts See Fig 8 Remote Start Contacts See Fig 8 Remote Local Cycling Devices See Fig 9 Multi unit sequence See Fig 10 1 The OptiView Control Center...

Page 2: ...ndividual shall also be familiar with and comply with all applicable governmental standards and regula tions pertaining to the task in question safety symbols The following symbols are used in this do...

Page 3: ...L OPERATION INDIVIDUAL UNIT PUMPS 9 FIG 15 MULTIPLE UNITS TWO PARALLEL OpERATION SINGLE CHILLED WATER PUMP 9 FIG 16 REMOTE Steam Hot Water Limit SETPOINT with 0 10vdc signal 10 FIG 17 REMOTE Steam Hot...

Page 4: ...R14 2 R58 R52 R50 R40 R38 R22 C8 R16 CR5 R56 R60 R54 R44 R42 R34 R36 R32 R26 R28 R24 R20 R18 R17 R1 R13 U1 U4 U3 R3 R15 R11 U5 R5 C1 CR2 CR3 CR8 RV7 CR7 RV6 CR6 RV3 RV2 R30 R2 Q2 R10 R4 U2 R12 R6 U6...

Page 5: ...View Control Center is in digital analog or ISN remote op erating mode allow ing for energy management system or remote start stop control Fig 8 2 All chiller safety cut out controls are in the normal...

Page 6: ...D06824 N O CONTACTS IN CONTROL CENTER RATED 2 AMPS INDUC TION AT 250VAC 30VDC 5 AMPS RESISTIVE AT 250VAC 30VDC closure of the Energy Management System Remote Stop Contacts causes the chiller to shutdo...

Page 7: ...l type flow switch is used the flow switch uses the cooling effect of liquid to sense flow When the flow of liquid is sensed the solid state relay output is turned on conducting current through the mi...

Page 8: ...tat RWTwill automatically cycle either 1 or 2 unit Timer 3TR is an additional feature which prevents simultaneous starting of lead and lag unit following a power failure and eliminates nuisance starti...

Page 9: ...p is avoided When one unit is cut out by the sequence control Fig 12 the temperature of the supply chilled water does not change MULTIPLE UNITS TWO PARALLEL OpERATION SINGLE CHILLED WATER PUMP For thi...

Page 10: ...inputs as follows Example if the input is 3VDC the setpoint would be set to 73 as follows SETPOINT 100 3 x 9 100 27 73 Therefore a 2 second pulse 10 3 sec 20 4 sec 30 up to 11 sec which will 100 Calc...

Page 11: ...rammed a setpoint for 44 F base into the OptiView control center and the Remote Reset Range is programmed to be 10 F then the energy management system can remotely reset the setpoint over the range of...

Page 12: ...et Range setpoint is for 10 F and the local Leaving Chilled Liquid Temperature Setpoint is programmed for 40 F the setpoint would be set to 44 F as follows OFFSET F 5 1 10 10 4 10 10 40 10 4 F SETPOIN...

Page 13: ...following message SAFETYSHUTDOWN MANUALRESTART and the cause of shutdown RUN CONTACTS REMOTE RUN LIGHT AND SHUTDOWN INDICATOR PLUS EMS When run contacts are required for a Remote Run Light and or Shu...

Page 14: ...is flowing the flow switch con tact will close If the flow switch opens for 2 seconds the unit shuts down GENERATOR BACKUP TRANSFER During a prolonged power failure the unit will shutdown without goin...

Page 15: ...and TB6 in YORK OptiView Control Center as 115VAC source is fed from terminals 1 and 2 16 Entering and Leaving Chilled and CondenserWaterTem perature Sensors are supplied by YORK as a standard item on...

Page 16: ...861 1001 www york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by Johnson Controls Inc 2009 ALL RIGHTS RESERVED Form 155 21 W2 1209 NEW...

Reviews: